Ask Experts Questions for FREE Help !
Ask
    TerryBlackman's Avatar
    TerryBlackman Posts: 1, Reputation: 1
    New Member
     
    #1

    Jan 22, 2018, 11:06 AM
    What size wire for 200 amp 280 foot away and what size ground?
    What size wire for 200 amp that is 280 foot away and what size ground. Also what size conduit for it?
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Jan 22, 2018, 02:35 PM
    Okay, first of all, is this a 200 amp load for a single family home or for some other use?

    Just working with the raw measurements you gave us and assuming that you want 200 amps at the terminus end of the run and given the cost of copper I'm using Aluminum as my conductor. Also, I am doing my guesstimate using lateral (underground) connection.

    You will need 3 ea. 500 kcmil THHW insulated conductors along with a #6 AWG bare copper equipment ground. You will also need Trade Size 4 Schedule 40 PCV conduit.

    If you are attempting to feed a remote building from a main panelboard for an existing building all of the above would be true, but the grounding at the secondary building would be different.

    Or you could consider having the power company put an overhead drop and transformer for you.
    hfcarson's Avatar
    hfcarson Posts: 1,003, Reputation: 49
    Ultra Member
     
    #3

    Jan 23, 2018, 10:40 AM
    the more you tell us the better the answer...
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #4

    Jan 23, 2018, 06:03 PM
    Or underground and Transformer?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

What size wire in the ground bushing [ 1 Answers ]

I have 3 parallel runs of 400 kcmil in 3.5" conduits for a 1000 amp service. What size wire do I need for the ground bushings?

How to bond and what size grounding wire and ground rods to use [ 6 Answers ]

200 amp meter outside to a service panel inside how to bond?

What size ground wire do I need for a 10 mega-Hertz ground 400 feet long? [ 1 Answers ]

We are adding a new ground that is 400 feet away, and we need to size it for 10 mega-Hertz. Can you please tell me the size cable that we need to install?

What size of ground wire for 200 ampere service in Canada. [ 2 Answers ]

What minimum size AWG copper wire require to install with 200 Ampere service in Canada?

Above ground pool: Wire size and burial method? [ 3 Answers ]

Hi, I'm planning to run a pair of circuits to the backyard for an above ground pool. The pool pump + salt cell requires a 20 amp @ 120 volts circuit, and I calculated that #8 AWG conductors are required to keep the voltage drop below 3%; the run is about 190 feet. The second circuit will only be...