    What size circuit breaker?
    Finally installing electric garage heater that I have been asking questions about recently. Instructions say that heater draws 31.9 amps and that 6 gauge wire is required. That's all fine, however, my question is what size 2 pole breaker should I use, 50 or 60 amp? If it is any help, it is a 7.5 KW unit. Hope to finally rap up this project because it is getting cold fast here in New Jersey. Once again, thank you all in advance for your help.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Oct 17, 2009, 03:41 AM
    50 amp will be fine. Based on the load, I don't see why a 40 amp would not work also. I wonder why they insist on #6 wire.
    nick jr's Avatar
    nick jr Posts: 27, Reputation: 1
    New Member
     
    #3

    Oct 17, 2009, 05:05 AM

    Thanks again for the help. I don't know why they require 6 ga. Wire. My only guess is because of heat. The electric heaters are very hot. Thanks again.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Theory of vacuum Circuit Breaker & sf6 circuit breaker [ 15 Answers ]

I want to know about the basic Theory of vacuum Circuit Breaker & sf6 circuit breaker

Circuit Breaker Size [ 6 Answers ]

I have a 48A 240VAC instantaneous water heater. What size circuit breaker do I need? I am thinking a 50A would do because it is not continuous.

What circuit breaker size should I use? [ 12 Answers ]

I recent purchased a heater that is rated 42.2 amps @ 240 volts. I was told by a licensed electrician that 8 awg would be fine for the heater. I have read some forums and now am questioning that also. I am wiring it in @ 220v So my questions are. Will it pull more amps @ 220v and if so how much?...

Circuit breaker size for several 300 watt flood light [ 10 Answers ]

I like to install 4 sets of flood lights. Each set is a pair of 150 watts bulb, for a total Of 300 watts per set, for a grand total of 1,200 watts for all 4 sets. Can I put all 4 sets of flood ligts on a 15A circuit? This is the way I like to install them: 2 sets of flood lights for the back...


View more questions Search