Ask Experts Questions for FREE Help !
Ask
    Eladsamoht's Avatar
    Eladsamoht Posts: 7, Reputation: 1
    New Member
     
    #1

    Mar 19, 2014, 08:52 AM
    What size of cable should I use to feed a sub panel in garage?
    I have buried 1-1/4" conduit from house service panel to garage 26" deep; The conduit does go solid from service panel in basement to sub panel in garage. I am planning on putting in a 100 amp sub panel in garage; I have the permit in hand; I plan to use 2 grounding rods 10' apart with # 6 grounding wire placed in the pole barn/garage. Two questions.. Is it best to use 2-2-4 alum cable to feed the sub panel or use copper? And can I add two runs of 14-3 inside the 1-1/4" conduit to hook up two 3 way switches for a couple of garage lights?
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Mar 19, 2014, 10:35 AM
    Okay, we need to know the type of conduit along with the conductor sizes to let you know for sure. (RMC - IMC - Sched. 80 PVC - Sched. 40 PVC) The inside diameters are different.

    Copper is a better conductor than Aluminum. If you use copper, the size of the conductors will be smaller. However, Aluminum is fine for this application. Remember you must use a four conductor cable from the main service panel to the panel in the garage. (Black - Red - White - Insulated Ground).

    At the panel in the garage, Neutral and Ground cannot be bonded together. They
    MUST be isolated from each other. They cannot be bonded together at the garage panel!

    Also, do not run the 14/3 cables with the feeder to the panelboard. Instead use a panelboard in the garage that will accommodate enough circuits for your need.

    The ground rods need only be 8' apart, not 10'.
    Eladsamoht's Avatar
    Eladsamoht Posts: 7, Reputation: 1
    New Member
     
    #3

    Mar 19, 2014, 10:57 AM
    Thanks for your reply; It is sched 40 pvc; the electrical inspector told me I could run 3 wire through the conduit as long as I put two grounding rods at the garage connected to garage panel with #6 bare copper wire; don't remember what he said about bonding; I was hoping to put the 2 runs of 14-3 from house to garage to connect two 3-way switch circuits to operate two separate lights from house or garage... Would I need to bury another conduit to accommodate the two 3-way switch circuits? And do the 14-3 wires need to be uf if inside conduit?
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #4

    Mar 19, 2014, 11:22 AM
    Sorry, but the electrical inspector is incorrect. Because this is a detached building your are required to do a four wire feed to the panel. See NEC Article 250.32.

    I believe the code changed in either 2005 or 2008 mandating that requirement. The grounding system at the garage still has to be there. The ground rods are for protection against lightning.
    Eladsamoht's Avatar
    Eladsamoht Posts: 7, Reputation: 1
    New Member
     
    #5

    Mar 19, 2014, 12:26 PM
    Thanks Don,
    Still, can I put the 14-3 wires in the same conduit for the 3-way switches in the house; I'm not sure how to go about getting the 14-3 romex to the house switches. I thought it would be nice to be able to turn on the outside light from the house. I will go to the 2-2-2-4 .
    Thanks again,
    Tom
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #6

    Mar 19, 2014, 01:04 PM
    Quote Originally Posted by Eladsamoht View Post
    Thanks Don,
    Still, can I put the 14-3 wires in the same conduit for the 3-way switches in the house; I'm not sure how to go about getting the 14-3 romex to the house switches. I thought it would be nice to be able to turn on the outside light from the house. I will go to the 2-2-2-4 .
    Thanks again,
    Tom
    You cannot use NM "Non Metallic" cable (Romex) cable in an outdoor conduit. NM cable is listed for "Dry locations" Underground conduit is a "Wet location"

    You can use Type UF cable or any of the conductors (individual) that are listed for use in a Wet location. Also, by code, you are required to have a light at the entrance door of the garage which is not the auto doors.
    Eladsamoht's Avatar
    Eladsamoht Posts: 7, Reputation: 1
    New Member
     
    #7

    Mar 19, 2014, 02:09 PM
    Quote Originally Posted by donf View Post
    You cannot use NM "Non Metallic" cable (Romex) cable in an outdoor conduit. NM cable is listed for "Dry locations" Underground conduit is a "Wet location"

    You can use Type UF cable or any of the conductors (individual) that are listed for use in a Wet location. Also, by code, you are required to have a light at the entrance door of the garage which is not the auto doors.
    Don,
    Thanks again.. you've been a great help... the light above the entrance door is one that I wish to hook up to a 3 way switch in house, the other 3-way is for the outside light at the peak on the front... I have a 10' carport running the full 48' length of my garage which will have 5 to 6 recessed can lights in the ceiling of the carport... I will plan on using two 14-3 UF and one 2-2-2-4 alum cable...
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #8

    Mar 20, 2014, 04:12 AM
    Quote Originally Posted by Eladsamoht View Post
    ...the electrical inspector told me I could run 3 wire through the conduit as long as I put two grounding rods at the garage connected to garage panel with #6 bare copper wire; ..
    It's infuriating when even an inspector does not know what he's talking about.
    The ground rods have nothing to do with the ground wire running with the circuit to the sub-panel. You need them regardless if you used to run 3 wires or 4. Now 4 is mandatory.
    hfcarson's Avatar
    hfcarson Posts: 1,003, Reputation: 49
    Ultra Member
     
    #9

    Mar 20, 2014, 04:29 AM
    ... the electrical code reference is 250.32(B)(1), with a good exhibit 250.19 in the handbook which shows what Don and Stan have said...
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #10

    Mar 20, 2014, 05:57 AM
    I'm sorry, I misread your switch issue.

    Yes, the 14/3 can go into the conduit along with the feeder. Switches only interrupt the ""Hot" leg of the circuit. Also, the code require that a Neutral connection is provided at the switch outlet. There are links on this forum showing you how to wire three way switches.

    Two excellent resources for residential wiring (albeit expensive) are "Electrical Wiring - Residential 18th. edition" Ray Mullin & Phil Simmons and "Electrical Systems" by Mike Callanan and Bill "W". Both are based on the 2014 edition of the code. Ray Mullin's book is laid out a little better but either will be great for your use.
    Eladsamoht's Avatar
    Eladsamoht Posts: 7, Reputation: 1
    New Member
     
    #11

    Mar 21, 2014, 06:38 AM
    Quote Originally Posted by donf View Post
    I'm sorry, I misread your switch issue.

    Yes, the 14/3 can go into the conduit along with the feeder. Switches only interrupt the ""Hot" leg of the circuit. Also, the code require that a Neutral connection is provided at the switch outlet. There are links on this forum showing you how to wire three way switches.

    Two excellent resources for residential wiring (albeit expensive) are "Electrical Wiring - Residential 18th. edition" Ray Mullin & Phil Simmons and "Electrical Systems" by Mike Callanan and Bill "W". Both are based on the 2014 edition of the code. Ray Mullin's book is laid out a little better but either will be great for your use.
    I have just returned from home depot. I bought a 500' coil of 14 solid to run 6 lines along with the feed; I am planning on putting different colored tape on each run to identify which is which... Is it OK to use the 6 solid IPO the 2 runs of 14-3?; Can I ground the switches in the house to the house service panel ground bar? Or should I go back and get a roll of 14-3 w/grnd? I will use which ever is better... Thanks... Tom
    Eladsamoht's Avatar
    Eladsamoht Posts: 7, Reputation: 1
    New Member
     
    #12

    Apr 6, 2014, 04:01 PM
    Thanks for your responses... I have run the 2-2-2-4 alum use cable through the conduit with no other wires. I plan to use a wireless 3 way switch for the outside light... thanks.. again... tom

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

What size amp to use to feed sub panel? [ 2 Answers ]

I added a 100 amp sub panel in my house. I am using a main breaker panel with 60 amps. I need to know what amp breaker to use from my main 200 amp panel to feed my sub panel. Also, I am using #6-3 Thanks

70 a sub panel with two 15a breakers what size breaker to feed panel [ 2 Answers ]

70 a sub panel with two 15a breakers what size breaker to feed panel

How to size a sub panel in my garage [ 2 Answers ]

I have a 100 amp panel in the house and I have to run 30 feet to my garage and I need a 20 amp for the compressor one 20 amp for a welder and a 15 amp for lights and a 20 amp for 8 recpeticals I do have #4 aluminum will this work for a 50 amp sub panel or what size sub do I need to have

Generator underground feed cable size [ 18 Answers ]

I need to install a 175 foot underground feed between a generator and a building and need help with finding the wire. My research indicates I can use either a copper 2-2-2-4 thhn or aluminum 00-00-00-1 thhn in a grey schedule 40 conduit. Is my research correct? What is the precise desingation...


View more questions Search