 |
|
|
 |
New Member
|
|
Aug 23, 2009, 01:05 AM
|
|
What gauge wire do I need?
What gauge wire do I need to run a 100 amps from my house to my shed that is 270 feet away?
|
|
 |
Printers & Electronics Expert
|
|
Aug 23, 2009, 04:38 AM
|
|
120 VAC, copper = 4/0 (#8 EGC). Al = 300 kcmil. (#6 EGC)
240 VAC, copper = 1, (#8 EGC) Al, 1/0 (#6 EGC)
|
|
 |
Uber Member
|
|
Aug 23, 2009, 05:01 AM
|
|
Don, and Burgertown, when line conductors are increased in size due to voltage drop, the EGC must be increased in size proportionally.
You have given sizes based on single voltages, but the service voltage is 120/240, and some loads may be 240, while others may be 120 volt.
Some loads may be just lights or small hand tools, while others, don't know without asking or assuming, maybe a large motor or welder. So need to determine types and voltages of loads
Now what?
Perhaps a compromise of using #4/0 Aluminum, 4 wire URD direct burial cable, with a reduced neutral of #2/0?
This is a common standard product available at a reasonable cost.
|
|
 |
Electrical & Lighting Expert
|
|
Aug 23, 2009, 05:58 AM
|
|
Depending on the actual load, I come up with some different numbers.
This is one of the few places TK and I sort of disagree. I feel a feeder should be calculated at 240v since as the load increases it actually becomes more balanced. It is extremely difficult to heavily imbalance a residential 120/240v feeder. That is something you would have to almost do intentionally, which is not going to happen. And all 240v loads are already perfectly balanced.
The loads is the other thing. Everyone says "What wire do I need for 100A?", when what they almost always mean is what wire for a 100A sub-panel.
Using the "standard" 80% figure I come up with #1cu for the feeders. Like TK said, the ground also need to be increased. Without doing all the math, a #6 would be fine.
At a full 100A load that jumps to 1/0cu. Again, the full 100A number is something that will likely never get seen if maybe for a very short duration.
Burger, if you provide a little more detail than "What wire do I need for 100A" then we can give you even more detail.
|
|
 |
Uber Member
|
|
Aug 23, 2009, 06:12 AM
|
|
Was just making a point to Don, that there is more to it than appears, and judgments need to be made, of course, would be better to know as many details as possible.
While I do agree with as the 240 volt loads increase the panel gets more balanced, and the neutch current remains fairly low, my concern, of course, without knowing details of the types of loads, is that say a large 120 volt is the only load running, or by chance only 120 volt loads are on one leg,and the neutch has 30-40 amps running on it.
I wish here was a simple answer for these types of questions. There just is not.
Reality may be even though there is a 100 amp feeder, more likely the load will be minimal, and #2, maybe #1, aluminum will suffice. Who really needs 100 amps, in a shed? Must be one helluva shed.
|
|
 |
Electrical & Lighting Expert
|
|
Aug 23, 2009, 07:11 AM
|
|
 Originally Posted by tkrussell
Reality may be even though there is a 100 amp feeder, more likely the load will be minimal, and #2, maybe #1, aluminum will suffice. Who really needs 100 amps, in a shed? Must be one helluva shed.
Yeah, I was thinking the same thing. :D
|
|
 |
Printers & Electronics Expert
|
|
Aug 23, 2009, 10:37 AM
|
|
TK, how do you arrive at a 120/240 VAC for a 100 Amp load cable sizing?
Can you show me the formula you use?
Also, I assume (very dangerous) that this will always be a feed line to a sub panel. So in this instance, the question appeared to me that he was asking what is the size of the cable I need to feed a subpanel 270' away from my main panel.
|
|
 |
Uber Member
|
|
Aug 24, 2009, 02:50 AM
|
|
That is my point, there is no one formula for 120/240 volts. You need to know what 120 volt loads would be on at one time, and understand what phase or leg they are on, so as to accurately calculate what the unbalanced neutral amps would be to be able to size the neutral and either/or of the live legs.
Then the types of loads must be considered, as I have said before, large motors, welders, and high amp draw of inductive loads, which have high inrush starting amps.
And I am of the philosophy of having a conductor larger than what appears to be sufficient for an typical load, as who knows if and when more or additional inductive losd will be applied. Once the wire is pulled you need to live with it, or spend more money later.
Sizing wire for voltage drop requires knowledge, experience and judgment.
|
|
Question Tools |
Search this Question |
|
|
Add your answer here.
Check out some similar questions!
Wire service, wire gauge 100 amp
[ 9 Answers ]
I'm installing a 100 amp service in the backyard with a separate meter on a pole next to sub-suface power tranasformer. I have a 100 amp meter box on one side of the pole and a 100 amp braker panel with a 100 amp main breaker on the other side. I'm going to place in it a 15-20 amp breaker for gfi...
What gauge wire do I use?
[ 5 Answers ]
I'm wanting to run power from a 20amp breaker from my house to a small storage building 100ft away. All I want to run on this line is a fluorescent light and a small hand drill or small shop vac. What gauge wire do I use? 12 or 10ga?
Connecting 12 gauge and 14 gauge wire
[ 4 Answers ]
Is it ever acceptable to attach 14 gauge to 12 gauge wire? I have a remodel situation where I have a 20 amp/12 gauge wired circuit powering outlets only. I want to tap off the end-of-run outlet to power an electric-venting skylight. The skylight comes with 14/2 wire. Can I tap off the 20 amp...
Connecting 14 gauge wire and 12 gauge wires in the same blue box.
[ 2 Answers ]
I am wiring my basement. All the outlets are running off 2 independent 20 amp circuit breakers connected to each other by 12/2 wire.
I wanted to run some stubs off my 12/2 outlets. All each stub would do is run to a small light (max 180 watts) and of course a light switch. Since I ran out...
View more questions
Search
|