    What gauge copper wire to use with 100 amp breaker
    My husband and I are trying to put together a 100 or 125 amp breaker box on a pole to establish utilities to our home. We already have some 4 gauge copper wiring and we're not sure if this will support the amperage. Is there some kind of table or guide? The other thing is that the electric company must OK it. Will it?
    ac101's Avatar
    ac101 Posts: 463, Reputation: 57
    Full Member
     
    #2

    Sep 27, 2007, 01:52 PM
    I think #4 copper should be fine for 100amp not sure for anything larger until you get to 200amp which at least here in sc #2 copper is required. Here you also need a #6 copper for ground for 200amp service I think #8 should be okay for grounding 100amps. Most importantly check with your local building codes usaully permits are required for doing this type of work. This is from my best memory based on where I live . Wherever you are may have different requirements that I am unaware of. Im sure TK will be on later and he will no doubt have the answers if I have missed anything.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Sep 27, 2007, 02:55 PM
    AC is correct. For residential 100 amp feeder, #4 copper is allowed.

    The utility should be fine with it. Best to check with them before getting in too deep, as they may have other requirements.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire service, wire gauge 100 amp [ 9 Answers ]

I'm installing a 100 amp service in the backyard with a separate meter on a pole next to sub-suface power tranasformer. I have a 100 amp meter box on one side of the pole and a 100 amp braker panel with a 100 amp main breaker on the other side. I'm going to place in it a 15-20 amp breaker for gfi...

Splicing #6 gauge 40 amp wire [ 5 Answers ]

I am planning a kitchen remodel and am replacing a 27" hard-wired drop in range with a 30" range that requires an appliance cord to be installed with a receptacle. The circuit is 40 amp and the wire is #6 that is hard wired into the existing 27"range. I will need to install a 3 wire receptacle...

14 gauge wire on 20 amp circiut [ 1 Answers ]

Can I use 15 amp outlet on 14 gauge wire that goes into a split box that has 12 gauge wire that goes back to the fuse panel and has a 20 amp circiut

Wire size in a 100 amp breaker [ 1 Answers ]

I was wondering if a 2/0 wire will fit in a siemens 100 breaker? Thanks for your help

Question on 12 gauge w/ 15 amp breaker [ 2 Answers ]

Hello, Glad to have found this place. Just had a question regarding 12 gauge wiring. While I know it is unsafe to use 15 gauge for a 20 amp breaker, are there any safety concerns using 12 gauge wire on a 15 amp circuit breaker? Reason I ask is I had recessed lights put in my basement and had...


View more questions Search