    Weird voltage readings.
    I am trying to help a friend of mine with an electrical issue and I am not able to. He has a sun room that has a dedicated 15 amp circuit running to it but lost power in the sun room for the outlets and ceiling fan and outside light. I have tested the breaker and its getting 120V to neutral and ground. But when I test to the first outlet where the feed comes into the sun room I get 120V to ground and 117V to neutral, and if I test my hot coming in to the black and white wire going to the next outlet I get 30V on both... is this a open neutral or is my hot and neutral touching somewhere?? Im lost... any help you can give me is greatly appreciated...
    Credendovidis's Avatar
    Credendovidis Posts: 1,593, Reputation: 66
    -
     
    #2

    Jun 23, 2008, 07:52 AM
    First if the wiring has not been changed, and the problem was not there before, but has suddenly occurred :
    There is a bad connection between the neutrals in the (first) outlet where the in and out neutrals show a voltage difference.
    As a result the voltage on the not properly connected neutral lines starts to float by capacitive action or connected equipment, and reduces the difference between hot and neutral.

    If the wiring was changed and the problem occurred afterwards :
    As per the first suggestion, but now also check if anywhere the neutral and earth wires have been swopped. If that turns out to be the case, your earth is a poor one!

    Success !
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #3

    Jun 23, 2008, 08:16 AM
    Please try it this way.

    First, unplug all wires from the receptacles in the sun room. If a wall switch connects the to the light, turn the switch off. With everything off, take your voltage reading you should see any where from 132 to 118 VAC. If you do not, disconnect the wall switch. If it is a glo switch, the LED could be shorted out. I had the same problem the other day.

    Whit the switch disconnected, take your voltage reading.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #4

    Jun 23, 2008, 08:24 AM
    You can also take a reading from the good outlet neutral, to the bad outlet hot. If the reading is correct, then open neutral.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Free psychic readings? [ 3 Answers ]

Hi, in new here. I hopeing some one can give me a reading or point in the direction of someone who can. It concerns the health of my son. Please mail me or leave a link Thanks in advance for any help.

Weird receptacle tester readings [ 1 Answers ]

When using a standard 120V receptacle tester on all receptacles fed from a 600V/120V transformer all three lights appear. There is no indication of what this means. When tested with a multimeter all readings are proper. Receptacle tester is working properly when pluged into plugs from other...

Psychics readings [ 3 Answers ]

I would like a reading... Any psychics in the house?

Why are these readings and not 110? [ 13 Answers ]

I have taken the experts advice and borrowed a digital multimeter. I tested the red wires and they read 54.9, the 2 white with the black wire was 0 and the 2 black were 54.9. So with having 2, 3 way switches, if I connect the blue to the black which is the light and the black to the red, and the...

Psychic readings [ 80 Answers ]

Psychic,tarot,and love readings by maria One reading will convince you that I am the psychic you have been looking for. Contact me now for advice and answers in all areas of life of such as love,marriage,career,health,family,etc.thank you and godbless


View more questions Search