Voltage drop calculations
Hey guys,
Please check my math?
I need to push 120 VAC, 300 feet. Calculating for Voltage Drop of > 3%. I came up with a run of 300ft. #8AWG.
The load is not important for this question, it's purely a Voltage drop question.
|
|
|
Uber Member
|
|
May 21, 2008, 04:27 PM
|
|
How about a current? 20 A, 15 A, 0 A.
At zero amps any gage will do.
Cu or Aluminum?
|
|
|
Senior Member
|
|
May 21, 2008, 05:49 PM
|
|
Originally Posted by KeepItSimpleStupid
How about a current? 20 A, 15 A, 0 A.
At zero amps any gage will do.
Cu or Aluminum?
LOL! It's good to see a sense of humor!
I agree!
Don,
Post your current. (I love calculation questions--well sometimes! )
|
|
|
Electrical & Lighting Expert
|
|
May 21, 2008, 06:19 PM
|
|
Originally Posted by donf
The load is not important for this question, it's purely a Voltage drop question.
Sorry Don, the guys are right.
The load is not important, it's essential.
Without a load there is NO voltage drop.
|
|
|
Senior Member
|
|
May 21, 2008, 08:41 PM
|
|
Originally Posted by donf
Hey guys,
Please check my math?
I need to push 120 VAC, 300 feet. Calculating for Voltage Drop of > 3%. I came up with a run of 300ft. #8AWG.
The load is not important for this question, it's purely a Voltage drop question.
Don,
is there anyway you can show us how you would work the problem?
I have some questions for you (Assuming UF cable):
1. How would you calculate the distance of a 300 foot run. Do you multiply it by 2= 600 feet:cool:
2. What if you had a multi-conductor (two hots and a neutral). Does this make a difference in how you would calculate the distance of the run.:cool:
Note: Lets make this clear. I am not asking the question because I do not know. I do know!
|
|
|
Uber Member
|
|
May 21, 2008, 09:12 PM
|
|
Washington1:
Then for #2, I think you need to add, "for a 240/120 volt circuit", otherwise only you can solve it. We could be working in Burma with 230/400 mains.
|
|
|
Printers & Electronics Expert
|
|
May 22, 2008, 07:27 AM
|
|
Details, details, why would you want them? Brain dead moment. I guess I just assumed you all would read my mind which is apparently a "Flat line" at the moment.
The load is 20 amps, the medium is copper the distance is 300 ft.
The formula was Ed = KxIxLx2/CMA becomes: Ed = 144000/16510 = 2.6 VAC.
|
|
|
Uber Member
|
|
May 22, 2008, 08:06 AM
|
|
I get #3 copper 2.9V drop 2.4%. #4 copper is a 3.1% drop.
This would be a 20 AMP continuous load.
|
|
|
Printers & Electronics Expert
|
|
May 22, 2008, 08:31 AM
|
|
Got it, thanks, Ron. I typed the wrong CMA in, I typed faster than I read!
I get 2.7 VAC with a CMA of 52,630.
|
|
|
Uber Member
|
|
May 22, 2008, 10:10 AM
|
|
OK Don. Similar problem:
120/240 volt service, (2 hots, neutral, ground), Load is 20 A at 240V, 300 ft away, copper.
|
|
|
Senior Member
|
|
May 23, 2008, 04:46 PM
|
|
Originally Posted by KeepItSimpleStupid
Washington1:
Then for #2, I think you need to add, "for a 240/120 volt circuit", otherwise only you can solve it. We could be working in Burma with 230/400 mains.
True!
I guess I tuned-in too late!
|
|
|
Printers & Electronics Expert
|
|
May 25, 2008, 08:27 AM
|
|
Ron,
I came up with a Ed of 5.2 using a #4 AWG.
Here's the formula I used: Ed=(12)(20)(300)(3)/41742 = 5.2 (Max Allowed = 7.2)
|
|
|
Uber Member
|
|
May 25, 2008, 01:02 PM
|
|
Don:
The answer is exactly the same as you got before. No additional calculations were needed.
I guess you can call it a trick question. The answer might have been different if it was a 240 volt circuit, but it wasn't. It was a 240/120 volt circuit. The lower voltage prevails. Gotcha.
|
|
|
Senior Member
|
|
May 25, 2008, 01:08 PM
|
|
What is 240/120:)
|
|
|
Uber Member
|
|
May 25, 2008, 01:22 PM
|
|
It's L1, L2, N and Gnd. Between L1 and L2 = 240, Between L1 and N = 120, Between L2 and N = 120. So, 240/120 or 240 V 4-wire.
|
|
|
Senior Member
|
|
May 25, 2008, 01:28 PM
|
|
Originally Posted by KeepItSimpleStupid
It's L1, L2, N and Gnd. Between L1 and L2 = 240, Between L1 and N = 120, Between L2 and N = 120. So, 240/120 or 240 V 4-wire.
:eek:
Just joking with you keep!
Trying to patch-up froming giving you a bad mark! Wish I could erase it!:rolleyes:
|
|
|
Uber Member
|
|
May 25, 2008, 02:31 PM
|
|
Ok, 240/120=2
|
|
|
Senior Member
|
|
May 25, 2008, 02:35 PM
|
|
Originally Posted by KeepItSimpleStupid
Ok, 240/120=2
And all this time I thought it was 240/120=4-2
|
|
|
Printers & Electronics Expert
|
|
May 26, 2008, 06:21 AM
|
|
Whoa, the calculation has to change because the number of conductors is three not two. At least according to the formula I'm testing.
The formula given is Ed=K*I*L*3/CMA. Becomes Ed=(12)(20)(300)(3)/41742
Ed=5.2
Do you ignore the 240 VAC [ L(1) to L(2)] and only count the L(1) to N?
Why?
|
|
|
Uber Member
|
|
May 26, 2008, 12:11 PM
|
|
I can't answer your first question, but I can the second.
What if the circuit was loaded as 20 amps of 120 on L1 and 0 amps on L2?
You now have a 120 V, 20 Amp circuit and thus you have to calculate the voltage drop on 120 V.
e.g.. If it were 1% your after; 1% of 120 is 1.2 and 1% of 240 is 2.4, so that shows that the smaller voltage prevails.
You need to educate me on the 3 conductor thing and how would NM-B or and cable in conduit be any different. If the 240 was equally loaded then there would be no neutral current, so your really only using 2 wires or sharing the current within 3 wires.
Now if it were 3 phase, I'd say there are 3 conductors, but with 240 single phase, it doesn't make sense to count the grounded conductor (Neutral). But code,they could say count it. In any case, with a 2 wire or 4 wire 240 system the sum of the power losses will always be the same. e.g. L1,L2 = 20A, N=0; L1=20,N=20,L2=0; or L2=20, L1-0, N=20 or even L1=15; L2=5 and N=15. There is no extra heat no matter what the sharing is, but it has to handle the worst case of the very unbalanced L1 L2.
|
|
Question Tools |
Search this Question |
|
|
Add your answer here.
Check out some similar questions!
Voltage drop
[ 5 Answers ]
I will be running wire to my shop that is aprox 250' from the main elect box at the house. I would like to have 220 volts and 110 volts. The wire will be buried underground the average temp in my area in the summer is 100 degrees. What size wire should I use. I will be welding with a welder that...
Voltage Drop
[ 3 Answers ]
I am trying to illuminate a tunnel about 3000' long temporarily with 9- 400 Watt Metal Halide fixtures spaced about 320' apart. I have a 120/240 generator single phase that I will use to back feed a 240/480 volt transformer to deliver 480 volts, single phase to the tunnel lights. At 480 volts I...
Voltage drop
[ 1 Answers ]
The Voltage will drop after 150 meter wire ,how to sole the problem .
Thanks to all
Voltage Drop
[ 2 Answers ]
I have a 20 amp breaker;there are a total of 7 receptacles on this circuit with a 15 amp GFI on the first receptacle.
The first 5 receptacles in line work fine, the last two receptacles which are approximately 70 feet from the 5th receptacle flip the 15 amp GFI off when plugging in a drill. I...
Voltage drop
[ 2 Answers ]
How far can you run an electrical cord, that is plugged into a 20 amp circuit, and still run a circular saw? If the saw starts slowly, will that harm the saw?
View more questions
Search
|