    Updating service panel to 200 amp with feeder to 100 amp panel in old house
    I currently in the process of converting 1000 sq ft of attached garage into living space while doing this we are updating electrical service to 200 amp new service, there is 100 amp service in the old part of the house which will remain but need to be sub paneled from the new 200 amp service. I have read the forms on sub panels which most discuss needing to use a 4 wire with in the same building but not sure what size and am confused? Just what size wire do I need to use?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Nov 2, 2007, 08:53 AM
    To feed a 100 amp subpanel, you can use #2 aluminum 4 wire SER cable, if aluminum feeder cable is allowed in your area. Otherwise you can use #4 copper wire, in metallic cable called MC cable.
    melliam's Avatar
    melliam Posts: 2, Reputation: 1
    New Member
     
    #3

    Jan 22, 2014, 01:08 AM
    It does depend on length of run... 1000sqft garage is huge. Lucky you.
    I agree with tk, although I'd be inclined to use ACWU... not that expensive and the armored aspect gives you more flexibility (SER needs mechanical protection, like walls etc). Noticed this thread is ancient, but I'll just leave this as an option.
    hfcarson's Avatar
    hfcarson Posts: 1,003, Reputation: 49
    Ultra Member
     
    #4

    Jan 22, 2014, 05:02 AM
    What is ACWU?
    melliam's Avatar
    melliam Posts: 2, Reputation: 1
    New Member
     
    #5

    Jan 22, 2014, 10:14 AM
    http://www.southwire.ca/en/products/acwu.htm
    hfcarson's Avatar
    hfcarson Posts: 1,003, Reputation: 49
    Ultra Member
     
    #6

    Jan 22, 2014, 10:35 AM
    Ahh... good stuff!
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #7

    Jan 22, 2014, 10:56 AM
    Note the original post was 2007. Probably wired by now!
    hfcarson's Avatar
    hfcarson Posts: 1,003, Reputation: 49
    Ultra Member
     
    #8

    Jan 22, 2014, 11:07 AM
    Yeah, he knew..
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #9

    Jan 22, 2014, 03:42 PM
    I agree with tk, although I'd be inclined to use ACWU...
    Are you in Canada? We do not use this cable very much in the US if at all, and good luck finding it even in a supply house.
    SER only needs physical protection where subject to damage. Not every exposed installation is exposed to physical damage.
    I think that's what you call Tek cable? Does that give any more protection value than SER/NM? In the US MC cable has no more protection value than SER/NM.

    Edit: Yeah, I see the link is a .ca domain, so your suggestion applies mostly to Canada as opposed to the US. There are some differences so it would be good to note this next time you reply to a 7 year old thread. :)

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

200 amp panel feeding a 100 amp panel roughly 130' away [ 7 Answers ]

Hi all, We are building a apartment above the garage,my question is what size wire do I need to run from the 200 amp panel to the 100 amp panel roughly 130' away? I want to use aluminum wire as I think copper would be to costly. Thanks for your help in advance, Dude :eek:

200 AMP Service panel to 200Amp Sub Panel [ 1 Answers ]

I getting new 200Amp service to surface mount service panel. I want to run 2oo cable to bring it sub panel in my Garage which is approx 120Ft Run through ceiling. 2 Questions 1. Is there any ristriction on running a 200AMP inside house to garage ? 2. I got a dirt cheap subpanel that has...

100 Amp Subpanel from 200 Amp main panel [ 2 Answers ]

I want to install a subpanel to be used to supply branch circuits to a new kitchen, laundry, garage, and some additional lighting and receptacles. The 200 amp main panel is about 50 ft away but because of the obstructions, we'll need about 85 feet of cable to connect the 100 amp subpanel. Since...

Using 100 amp panel on 200 amp service [ 5 Answers ]

I am building new camp at a site that already has 200 amp service. My power requirements are small and 100 amp will be more than sufficient. Is there any reason I cannot hookup a 100 amp panel to the 200 amp meter socket? Not sure is code allows this. I want to use a small 100 amp panel vs the...

200 Amp Service Panel with 60 Amp Main Breakers [ 26 Answers ]

I was told when we purchased our house that it had 200 Amp service which it appears to be; however, the top of each bus bars only has 60 Amp breakers for the Main shut offs. Is this normal? Each bus bar is connected to a hot wire (one red and one black) and then the two 60 amp breakers are...


View more questions Search