    davidadrian140's Avatar
    davidadrian140 Posts: 124, Reputation: 2
    Junior Member
     
    #1

    Jun 1, 2010, 08:38 PM
    Type of wire needed for electric meter
    I have a 100 amp main breaker in my service panel. (not a sub panel). I'm changing the service panel to a newer 100amp panel. So I would like to change the wires coming from the meter outside to the service panel. The current wire is not in any type of pipe. It's three wires wrapped in a weather proof jacket. Can any one tell me what type and size wire I need to run. By the way I live in the Chicago land area.

    Thanks guys.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jun 2, 2010, 05:44 AM
    The cable you see is called SEC cable. #2 alumimum 3 wire cable is needed from the utility connection to the meter. Need to check with your local code if SEC cable is still allowed, or will conduit be needed.
    davidadrian140's Avatar
    davidadrian140 Posts: 124, Reputation: 2
    Junior Member
     
    #3

    Jun 2, 2010, 06:25 AM
    Quote Originally Posted by tkrussell View Post
    The cable you see is called SEC cable. #2 alumimum 3 wire cable is needed from the utility connection to the meter. Need to check with your local code if SEC cable is still allowed, or will conduit be needed.
    Thank you very much tkrussell. You have been very helpful. You guys are the best. Thanks again.
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #4

    Jun 2, 2010, 07:53 PM

    I would be surprised if Chicago didn't require it in conduit---seeing that it's their golden rule.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search


Check out some similar questions!

About electromegnet induction type energy meter [ 1 Answers ]

In electromegnet induction type energy meter why the rotating alluminium disk is perforated? Its surface is dotted and rough, why? Send me replay

Electric stove install wire size/type [ 4 Answers ]

I am installing a Peerless electric stove the plate on it says " Three wire 120/208 volt 60 cycle ac , wattage 8800. I have a GE powermark gold loadcenter with about 10 empty blanks for breakers. The loadcenter is about 75 to 80 feet from the stove location. What size/type wire should I use? What...

Are electric meter sided? [ 6 Answers ]

In other words, given a socket box, does it matter which of line or load is connected one side or the other of the meter? Regards --Campagne

Electric fireplace, wire needed? [ 1 Answers ]

I am going to put in a 10000 BTU, 3000 watt, 240 electric fireplace. I will be using about 15 to 20 feet of 12/3 wire with a 2 pole 20 amp breaker. Would that be a problem? Thanks

About electromegnet induction type energy meter [ 1 Answers ]

About electromegnet induction type energy meter -------------------------------------------------------------------------------- In electromegnet induction type energy meter why the rotating alluminium disk is perforated? Its surface is dotted and rough, why? Send me replay


View more questions Search