    Is there any reason for not running a total of 4 romex wires through a 1” conduit?
    Is there any reason for not running a total of 4 romex wires through a 1” conduit?

    I am rewiring 2 bathrooms and running the wiring from the crawlspace of the house. I need to run 3 12/2 romex (to 3 GFI’s) and 1 14/2 romex across the joists. There is no room for a running board and I do not want to bore holes into the joists. Is there any reason I could not run the total of 4 romex wires through a 1” conduit for 20 feet?


    There is about an inch of space because of the concrete block wall, other wires, HVAC, bathroom and kitchen plumbing intake/waste, telephone wires and whatever else I have left out. Everything going on in my house seems to be happening right in this area.

    Thank you.

    --------------------------------------------------------------------------------
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Sep 11, 2010, 05:27 PM

    Cynthia,

    Yes, NM cable can be run through conduit but not in your situation.

    Article 334.15(C) In Unfinished Basements and Crawl Spaces: reads in-part: "... Smaller cables must be run through bored holes in joists or on running boards."

    This is referencing cables less than 2, #6 or 3 #8. you are using #12 cables so that is what you are limited to."

    According to the same code cite, NM cable on the wall of an unfinished basement may be placed in listed conduit or tubing.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Sep 12, 2010, 05:01 AM
    Romex can be installed in conduit, however, 1" conduit is not large enough for 3 - #12-2 and 1- #14-2 cables.

    Don is interpreting the Section 334.15(C) a bit incorrectly, as if Romex could not be installed in conduit on the ceiling of an unfinished basement.

    The point that Section 334.15(C) is making is that Romex smaller than the 2- #6 or 3-#8 cannot be simply stapled on the bottom of the joists.

    You can do as you propose, however a much larger conduit would be needed. I do not recommend pulling Romex through any conduit of any distance greater than a few feet.

    What you can do is install a complete conduit system with boxes and connectors, and pull THHN wire through it, and junction to Romex at both ends if necessary where the cables would then branch off in their different directions.

    This can be a 3/4 inch conduit with 7- #12 (6 for the 3-#12-2 plus one for equipment ground) plus 2 #14 for the #14-2, using the one #12 equipment ground already provided.
    Cynthia02's Avatar
    Cynthia02 Posts: 2, Reputation: 1
    New Member
     
    #4

    Sep 12, 2010, 10:13 AM
    Sounds like the conduit is a bad idea. What about a running board attached to the conrete wall/foundation?
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #5

    Sep 12, 2010, 05:50 PM

    TK, I did not interpret anything. I quoted directly from the 2008 code book.

    Cynthia, please reread TK's post. Its not the idea of the conduit that TK is opposing.

    He is giving you a better way to accomplish what you want. Also he is letting you know that the 1" conduit is to small to hold all the wires you want to put in it. If you follow TK's solution you will be able to use a 3/4 trade size conduit.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Romex in PVC Conduit ? [ 26 Answers ]

Need to run #12 wire to my gate opener. Have 1" schedule 80 conduit in ground. Can I run 12/2 Romex through the conduit to feed the gate ? Or do I have to run individual wires. Thank You

Running romex in pvc conduit [ 3 Answers ]

Just bought 85 feet of romex #6/3 and 1" pvc conduit and was going to run from my house to a sub panel in my shed. Now I hear that's not the way have any sugestions? Guess I should have researched before buying materials.

Romex in conduit [ 3 Answers ]

I have 1/2" rigid conduit, can I run 12 AWG through it for a length of about 6'? It will be a single cable pull, and it has one 90 degree bend.

Running two wires through electrical conduit [ 4 Answers ]

I want to supply power to run some power tools and shop lights out in my detached garage which has no electricity at all right now. I want to run two separate circuits and I'm using a buried electrical conduit with the wires inside. Since it's two separate circuits do I need two conduits or can I...

Can romex be installed in a conduit [ 13 Answers ]

I am installing a new 100A sub-panel. The feed will be from main with a 100A dual-pole breaker. The main and the sub-panel are in the basement. The new sub-pnael Will be about 25 feet from main. I already bought the feed cable for this sub-panel. I bought #4/3 With Ground NM-B romex. The...


View more questions Search