    Temporary generator wiring
    I have a portable generator 6.5 kVA w/ 7500 watts single phase 120/240 type. It has a pair of 120 gfic outlets and one 4 twist type 240 outlet. I would like additional input on how to wire to house panel (100amp)w/ out a transfer switch. Understand during outage one would operate it in a standard mode ;but w/ main breaker in OFF position. Will this run my ac unit and refridge? What Wire type (3 or 4 wire) and plug type is needed to accomplish this ? Thank you for any input.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Sep 6, 2008, 12:14 PM
    You DO NOT do this!! What you propose is stupid, unsafe and ILLEGAL!

    There are reasons EVERY power company web site has warnings about illegally backfeeding your service.

    Get a transfer switch, transfer panel, or main breaker interlock, or just use extension cords to power up the appliances you need.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #3

    Sep 6, 2008, 12:37 PM
    Clarification:

    Main Breaker Interlock

    Prevents backfeeding to the utility. It interlocks the main breaker and the breaker for the generator so that both cannot be on at the same time.

    Second:
    You will need a generator input connector mounted on the outside of your house.

    Third:
    When using the generator powering the house, the neutral to ground bond in the generator should be removed. When independently operating the generator, it should be present.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wiring a generator to my panel [ 1 Answers ]

I was told that I can replace the front panel on my breaker box, with one that will plug into my generator. Where do I find such a panel cover?

Temporary custody [ 3 Answers ]

A friend of mine signed temporary custody of her son over to her sister while she was incarcerated.the sister was not taking proper care of child and came to visit and my friend the natural mother of the child would not let the baby leave with the sister.she brought the law up there but mother had...

Generator Wiring [ 2 Answers ]

I have a generator that puts out 5500watts & has (4) 120 volt 20 amp receptacles and 1 Nema L14-30 120/240volt receptacle. I am running a new wire to the panel so I can hook my travel trailer up. The RV requires a 30 amp 120volt receptacle. I have already purchased the wire and connectors but...

Wiring my home for a generator. [ 19 Answers ]

After a major ice storm going through and being with out power for days. I was told of a simple way to hook up a generator to my home. So I went to my trusty home store after already buying a generator. I bought the some #6 romex 3 wire with ground and a 30 amp two pole breaker and wired it...

Electric generator wiring [ 3 Answers ]

I have a DeVilbiss electric generator 5000 watt 120/240 volt @ 41.7/20.8 amp- it has a switch that connects the 240 volt . It has one 120 volt outlet and one 120 volt 4 prong receptacle. As stated , it has a switch to connect the 240 volt capability. What I want to do is make a new pannel for...


View more questions Search