    Subpanel in different building
    I have 400 amp service main panel. One subpanel in same building. Between panels do wires have to be in conduit, if
    They are in 2x6 wall and 2x12 sealing?

    2nd panel in another building 50' away, no metal bonding between them. Am I right with having separate ufer in this building for the grounding?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Jan 12, 2012, 04:36 AM
    Quote Originally Posted by billb7 View Post
    I have 400 amp service main panel. One subpanel in same building. Between panels do wires have to be in conduit, if
    They are in 2x6 wall and 2x12 sealing?
    Not unless your local codes require it.



    Quote Originally Posted by billb7 View Post
    2nd panel in another building 50' away, no metal bonding between them. Am I right with having separate ufer in this building for the grounding?
    A grounding electrode is required at a detached structure with a sub-panel. A ufer is the best type of electrode.

    This has nothing to do with the required equipment ground that you must run with the feeder conductors.

    Equipment grounding and grounding electrodes are two completely separate things with two completely separate functions.
    Grounding electrodes have nothing to do with clearing faults and tripping breakers on the secondary (120/240v) side.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

What does a building manager charge for a condo building per issue? [ 0 Answers ]

We would like to hire a building manager for our condo complex. We already have a property management company, but they only look after the financial budgeting. We need someone to attend to any problems with the building like noise complaints, landscaping on a per call basis or a regular fixed...

What does a building manager charge for on call serices for a condo building? [ 1 Answers ]

I have been asked by a property management company what I would charge to a condo board for on call resolve to building maintenance problems, noise complaints etc. They want to be charged per issue. Some things would require going on site to meet the trades and some issues could be resolved by...

Electrical subpanel fed from a subpanel: is this allowed? [ 1 Answers ]

Hello: Can I feed an electrical subpanel (or two) from a subpanel to the main? Thanks for your help!


View more questions Search