    Sub panels
    When installing a sub panel in a single family dwelling coming off a main panel do you size your wire as a feeder according to 310.15 (b) (6) or do you size it as a branch circuit?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Feb 18, 2008, 10:04 PM
    Depends on location.
    In my area we are allowed to use 310.15(B)(6) for 100A sub-panels. Meaning #2al or #4cu.
    I use #2SER ALL the time for 100A sub-panels.

    And NO, I don't want to get into the argument about whether this is allowed. Our AHJs allow it and that's all I've ever known around here.

    IMO it is common sense. In a residence a 100A sub-panel will have JUST as much load diversity as a main 100A panel, so why should a sub-panel be required to be fed with larger wire?

    Anyway, check with your local AHJ and see what he says.
    Worst case scenario, use a 90A breaker.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Feb 19, 2008, 06:47 AM
    As Stran states, there should be no reason not to use table 310.15 (B) (6), as this tables is for residential services and feeders, and a cable to a subpanel is considered as a feeder.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Adding sub panels and then some. [ 19 Answers ]

Hello I am a fully qualified carpenter/builder from Ontario Canada. I have done a number of my own electrical projects on my past homes and I enjoy the challenge. I was just surfing the site looking for some ideas on my situation and I was enjoying all the good advice that you well...

Electrical panels [ 2 Answers ]

I have a 200 amp panel and a 60amp service. I was wondering if I could upgrade to a 100amp service with out getting in troble from the hydro company or do I have to got to 200amp service? Thank you

Connecting two panels [ 1 Answers ]

We want to add another panel in our basement along side the original panel. This new panel has to have a 60 amp breaker and a 30 amp breaker with a 10 or 12-120 breakers. What size wire would be required to connect the two panes?

Multiple Sub Panels [ 1 Answers ]

First questions; I have a GE Box with 200 amp service. I have one sub panel and need to add 2 more. Is there a limit on how many sub panels that can be added? My home has gas heat and gas water and therefore total current is not a problem. Second question; My existing GE panel has horizontal...

Electric panels [ 3 Answers ]

This Is The Problem I Am Having I Have Two Electrical Panels In Side The House. The First Panel Is A 125 Maxium Rateing Murray & The Other Panel Is A Ge Panel Rated 120/240 Ac 3 Wire 125 Ampere The Murray Panel Has The Stove & Water Heater Wired To It.the Other Panel Has 20 Amp 30 Amp...


View more questions Search