    Sub Panel with a main in Position 2,4, 6
    My question concerns panel boards where the main breaker takes up two or three positions on the panel board. If I use a main in position 2,4,6 the corresponding positions 1,3,5 have to be left blank according to code.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    May 4, 2006, 03:07 PM
    No, the pole space opposite the main can be used for branch circuits, however the main breaker must be held in with a Main Breaker Retainer Kit, as per NEC 2002 edition, Section 408.16 (F) " plug in type devices that are backfed for supply ungrounded conductors shall be secured in place by an additional fastener that requires other than a pull to release the device from the mounting means on the panel"

    Unless of course the breaker extends into that space, which most do not do any longer.

    The retaining kit is different for each brand of circuit breaker/panel. Check with your breaker/panel supplier for the retainer kit.

    Ands be sure to use the label that comes with the panel to mark the main breaker as "MAIN".
    mike721's Avatar
    mike721 Posts: 4, Reputation: 1
    New Member
     
    #3

    May 5, 2006, 07:34 AM
    Thank you very much

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Main Service Panel needs [ 9 Answers ]

I ran across this site accidentally today and found someone who had many of the same issues I need help with. Most of my questions were answered reading the forum however I have one more, using the following information I am hoping someone can help. The existing house is apx. 2300 sq ft w/a 200...

AC Flexible ducts position [ 1 Answers ]

I have flexible AC ducts in my attic that just lay across the floor of the attic. Should these ducts actually be suspended in the air or does it really matter?

Entry level position [ 1 Answers ]

I'm a senior undergraduate bio major and I'm looking for an entry level position at a hospital after I graduate in the spring to gain more experience in patient care. In about a year I hope to go on to a master's physician's assistant school. Do you know of any positions where you don't need more...

How do I relocate a main service panel? [ 4 Answers ]

I need to move my main service panel about 20 feet. All of the branch feeder wires need to be longer to reach the new box. How do I extend them?


View more questions Search