    Sub panel circuits
    I Want to replace an existing unused 20 amp two phase electrical outlet with a sub-panel containing single phase 110 volt circuits with appropriate circuit breakers. My question is: How many separate circuits does the NEC allow in this type of sub-panel?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Nov 10, 2006, 08:10 AM
    When you say "two phase" , do you mean a single phase circuit with two hot legs creating a 240 volt 1 phase circuit? Just because there are two hots, does not mean it is two phase.

    If so, and the circuit/outlet is rated for 20 amps, any subpanel you install can have up to and no more than 42 circuits, however, the connected load can not exceed 20 amps, due to the rating of the feeder.

    Seems your limited to 20 amps.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

200 amp panel feeding a 100 amp panel roughly 130' away [ 7 Answers ]

Hi all, We are building a apartment above the garage,my question is what size wire do I need to run from the 200 amp panel to the 100 amp panel roughly 130' away? I want to use aluminum wire as I think copper would be to costly. Thanks for your help in advance, Dude :eek:

Circuits [ 2 Answers ]

Suppose that the switch has been closed for a length of time sufficiently long for the capacitor to become fully charged. (a) Find the steady-state current in each resistor. R1=16.00 kΩ, R2=12.00 kΩ, and R3=2.00 kΩ. (b) find the charge on the capacitor. 9.00V, 10.0uC I found part (a) but I'm...

Sub panel fed with two circuits [ 3 Answers ]

I was looking for space to add a circuit to an existing sub panel at my mother's house and ran into a problem that I need some advice on. Upon opening the sub panel, I discovered that it is being fed with two 12-3 Romex wires originating from two 20A circuits at the main. Now, I think that I...

New bathroom circuits [ 1 Answers ]

I am remodeling my 2nd floor bathroom and adding laundry (gas dryer). I replacing old circuits with 2 new circuits. One dedicated to washer/dryer and another for one outlet, 2 vanity lights, 1 general illumination light, and for the exhaust fan/shower light. Can I make one 12/3 run from my...

Testing circuits [ 4 Answers ]

Anybody have creative ideas on how to test light and receptacle circuits in a brand new house that does not have power yet from the utility company. The sub panel is complete with all the wires and circuit breakers connected. All the receptacles and lights switches are installed. Has anyone...


View more questions Search