    Should I bond sub pannel if not using a neutral
    I have sub pannel for my two welders 30amp and 50 amp. I am basically using this as a junction box. Each welder has its own breaker. I ran 220 with a ground for this with no neutral. Will only be used for the welders. My question is should I use the bonding screw to bond the pannel to ground or just leave it floating.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Feb 8, 2010, 10:43 AM

    First major question, is the sub-panel you are speaking about in the same building as the main service panel or is it in a different building?

    If the sub-panel is in the same building, then you can use the existing grounding system at the main panel a do not "Bond the Sub-Panel". Sub -panels should be fed by a four conductor cable. Two hots, Neutral and ground.

    If the sub-panel is in a separate unattached building, then the code is more specific.

    You are required to run a four wire feed from the Main Service Panel to the Sub-panel. 2 Hots, Neutral and ground. The sub-panel is required ti use its own grounding system made up of one or two ground rods no closer that six feet from each other.

    Also, you cannot bond the Neutral and Ground together in a sub-panel. Neutral must be isolated from Ground.

    If the sub-panel has more than 6 breakers you need to protect the garage/shop by using a "Kill Switch" to kill power to the sub-panel or a main circuit breaker on the sub panel.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Why do we need to bond neutral & ground in breaker box [ 5 Answers ]

I have noticed that in the Main breaker box we bond the neutral and ground togather. The questions are; 1- Why do we need to do so. 2- If I plug my drill in to any grounded outlet, why the ground wire is not carring any current as the neutral does and we can touch ground wire where as we can't...

Pannel box [ 3 Answers ]

I have added a 220 stove to a house that I want to rent. I ran the electrical wire correctly from the pannel box to the new stove. I bought a new 50amp breaker for the pannel box but only the light's turn on at the stove. I had the stove checked and it is in perfect condition, it's new. The folk's...

What happen if you connect some grounds and neutral to the neutral bus bar and the do [ 1 Answers ]

The same conect some grounds and neutrals to the ground bus bar just using whichever bus bar is closest to the breaker so the wires don't have to travel all around the breaker box is that OK and safe to connect wires like that thank you

Should I bond neutral and ground in my box? [ 1 Answers ]

I have just had 3 cables of #4 aluminum wire run from my main panel to a new sub panel in my shed. I have them wired as 2 hot, 1 neutral. Maybe I should have run a fourth wire for ground, but too late for that since its buried 2 feet down. With three wires coming from my main to my shed, do I...

Neutral to Ground Bond [ 4 Answers ]

This should be a straightforward question and answer but so far everyone I've asked has given me the "it's a local code issue" or in my opinion the wrong answer. I have a 12KW standby generator permanently installed at my home. The ATS is a two-pole transfer with a solid neutral. The generator...