    Secondary 100 Amp Feeder Wire Size
    Hello to all. I am running a feeder wire in 2" conduit from my 100 amp breaker in my house panel to my 100 amp garage panel approximately 160' away. I am wondering if #1-#1-#2 Aluminum is sufficient with a #6 Copper ground. Thanks for the help.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Feb 22, 2007, 03:30 PM
    The voltage drop will be 6.5 volts across each 120 leg to neutral assuming the load is 80 amps.

    Recommended maximum allowance is 3% or 3.6 volts. If the load does not exceed 40 amps, the voltage drop will be 3.2 volts, which will be acceptable.

    If there will be large motors, say 5- 10 HP, they may have a problem starting due to the locked rotor amperage combined with any other running load.
    jeff bouchey's Avatar
    jeff bouchey Posts: 7, Reputation: 1
    New Member
     
    #3

    Feb 22, 2007, 04:50 PM
    Quote Originally Posted by tdcalahan
    Hello to all. I am running a feeder wire in 2" conduit from my 100 amp breaker in my house panel to my 100 amp garage panel approximately 160' away. I am wondering if #1-#1-#2 Aluminum is sufficiant with a #6 Copper ground. Thanks for the help.
    Yes # 2 Al or #3 Cu is sufficient. #6 Cu ground is also sufficient. Just remember to remove the bonding screw in the panel in the garage. I suggest burying a ground plate approx. 2' in the ground and tying it to the panel itself
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Feb 22, 2007, 05:12 PM
    Do not connect the new panel to a grounding electrode as suggested.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Condo/Apt. New 100 amp service - BX wire size? [ 12 Answers ]

Hi All! I currently have an old 40 amp service in my pre-war condo. We are allowed to run BX securely attached for a new service. The distance is 250 feet. I am looking to get a 100 amp service. What size BX cable should be used for this? Do they make BX large enough for a 250 foot 100 amp...

Feeder size [ 1 Answers ]

Hi, We are building a small art studio in our backyard. The power requirements for the building are: 1 dedicated 110V 20 amp circuit for a small kiln 1 dedicated 220V 20 amp circuit for a larger kiln 1 dedicated 110V 15 amp circuit for small wall-mounted heater/ac unit 1 dedicated 110V 15...

Wire size in a 100 amp breaker [ 1 Answers ]

I was wondering if a 2/0 wire will fit in a siemens 100 breaker? Thanks for your help

Wire Size For 200 Amp Service [ 2 Answers ]

Recently purchased new mobile home with a 200 amp breaker inside.the distance between the outside pole and inside breaker is about 70 feet.what size,or type,or gauge wire do i need to run. Lost in paradis... :) :confused:

How do I figure out what size wire to use on a 200 amp service. [ 2 Answers ]

My question is... how do I figure out what size wire to use when I know the Amperage of the electrical device. Is there some form of electrical calculation? For example I want to upgrade to a 200 amp panel from a 70 amp panel.


View more questions Search