    Running power to a outbuilding, do I need a separate disconnect?
    I am running power to an outbuilding, and was told I need a separate power disconnect on the outside of the building before the service entrance panel. Something about Firefighters need access to the power, on the outside of the building. Is this a new code I'm unaware of?
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Apr 21, 2011, 05:50 PM

    It is not part of the NEC, however, that said, it may be a requirement of the LAHJ.

    Does your home currently have an outside disconnect switch on it?

    It not such a big deal. You just run your four wire feed to the switch and then from the switch to the inside panel. I would also advise you to either use a panelboard with a main breaker on it or install another switch in case of an emergency you can shut the power off in one movement.
    sawsall02's Avatar
    sawsall02 Posts: 55, Reputation: -4
    Junior Member
     
    #3

    Apr 21, 2011, 06:16 PM
    Comment on donf's post
    Hey donf, yes both the house and the barn have panelboards with main breakers. No disconnect on the outside of home other than the meters. Thanks.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #4

    Apr 21, 2011, 06:33 PM

    Okay, but that does preclude the possibly of a new local code having been implemented.

    To be real honest with you, most of the fire-people I know prefer to know for sure all of the electrical power has been cut off to a building before then enter it an start running around shooting water every where.

    My brother was with the NYFD for 20 some years and I have both a nephew and a niece on the fire departments of two neighboring cities. It seems they have no interest in getting shocked to death, go figure :)
    sawsall02's Avatar
    sawsall02 Posts: 55, Reputation: -4
    Junior Member
     
    #5

    Apr 21, 2011, 06:54 PM
    Comment on donf's post
    Yea, I've got a buddy that's on the DFD here in Michigan. Would"nt want to see anyone get electricuted. Just wondering if it's code in Lenewee county, MI. though? Power could always be shut off at the house to the barn. I guess the reasoning is, for if you were not home if a fire did start.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #6

    Apr 22, 2011, 06:02 AM

    It's a simple matter to find out if an exterior disconnect is required.

    Call the city or state inspectors and ask them. For that matter you could probably call the fire department in your area and see if they have mandated that disconnect.

    As far as I know, if any fire crew, someone is specifically detailed to get the power off in the building.

    Whether the disconnect is inside or not.
    sawsall02's Avatar
    sawsall02 Posts: 55, Reputation: -4
    Junior Member
     
    #7

    Apr 22, 2011, 06:42 AM
    Comment on donf's post
    I'll do just that, thanks donf.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #8

    Apr 23, 2011, 03:56 AM
    I cannot find any specific code for your county.

    I can find the electric code for Michigan, which adopted the NEC 2008 edition Dec2, 2009, with specific amendments unique to Michigan:

    http://www.michigan.gov/documents/dl...n_295688_7.pdf


    From the 2008 edition of the NEC:

    VI. Service Equipment — Disconnecting Means

    230.70 General. Means shall be provided to disconnect all conductors in a building or other structure from the serviceentrance conductors.

    (A) Location. The service disconnecting means shall be installed in accordance with 230.70(A)(1), (A)(2), and (A)(3).

    (1) Readily Accessible Location. The service disconnecting means shall be installed at a readily accessible location either outside of a building or structure or inside nearest the point of entrance of the service conductors.


    So, your outbuilding does need a service disconnect at that building, NEC allows it to be inside or outdoors.

    Having it outdoors is better, I believe, for access and easier to install.

    Firefighters will always appreciate a disconnect outdoors, but they do not usually have the opportunity or legal authority to dictate it is required to be outdoors.

    While it would seem easy to require all service disconnecting means to be located outdoors, there are too many locations this requirement would just not work, or be practical, for many reasons, therefore, cannot be restricted by a wide brush requirement.
    sawsall02's Avatar
    sawsall02 Posts: 55, Reputation: -4
    Junior Member
     
    #9

    Apr 23, 2011, 07:01 PM
    Comment on tkrussell's post
    Thanks tkrussel, Already have one inside, so I should be O.K.. I have it located as soon as you come in the front entrance door.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

How can I separate my power to the exhaust fan and bathroom light? [ 1 Answers ]

I have my fan and wall light connected to a single switch.so when I turn light on ,the fan goes on. I want to put a double switch in and have one switch control the fan and the other the light. Keep in mind the fan is not a part of the light. Fan is on ceiling, light is on wall

I am running a 60 amp double pole feeder to my outbuilding. [ 9 Answers ]

I am running a 60 amp double pole breaker to my outbuilding 190' away. I figure I should use #4 copper use wire for the ungrounded conductors. The legs in my subpanel figure to 42 amps on one leg and 29 on the other if my calculations are correct. These are figured on 180 va for duplex outlets (20...

Disconnect a power vent [ 3 Answers ]

I built a chimney to replace a stinky power vent on an oil burner.Besides venting the 6-inch smoke pipe into the chimney what do I disconnect or change on the power vent?

Power To An Outbuilding [ 2 Answers ]

I have a barn that is 300 feet from my house & I want to install 4 or 5 lights plus a power outlet. What size wire & breaker would I need to do this in a satisfactory / safe manner. Many Thanks

Electric Power to Outbuilding [ 3 Answers ]

My house has 200 amp service. I am running power to my new shed 250 feet from the house and need no more than 60 amps. What size wire (direct bury) do I need and should I be looking at copper or aluminum? Also, is there a formula to calculate the wire size based on amps, distance, voltage...


View more questions Search