    Run the GEC in same conduit with SubFeed Conductors?
    I am backfeeding a 200 amp service with 4/0 AL XHHW conductors in a 2.5" Rigid PVC conduit to a J-Box and then continuing through the basement with SER. I would like to run the 1/0 CU GEC with my subfeed conductors through the PVC. At the J-Box, the GEC would continue to the water pipe. The water pipe is located in the same direction as the 200 amp subpanel. Are there any NEC rules prohibiting this approach?
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Apr 23, 2011, 03:03 PM

    I guess I'm obtuse today because you are not making sense to me.

    The NEC requires that the service entry conductors connect with the Main Service Panel as close a possible to their entry point into the building.

    Next, the NEC cites the cold water pipe as the primary grounding electrode and requires a supplementary ground rod.

    The connection of the EGC must be within 5' of the entry point of the cold water pipe and to qualify as an acceptable the metal cold water pipe must extend at least 10' into the earth.

    Can you tell us if you are trying to set up the main service panel or running a feeder to a secondary panelboard.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Apr 24, 2011, 03:57 AM
    There is no restriction to do as you plan, just be sure the GEC is continuous, with no splices.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

I have romex installed in a conduit for about an 8ft run. Is this OK? [ 2 Answers ]

I upgraded my garage to add a couple of receptacles. The bulk of the wire is running through the rafters of my basement, but I enclosed about the last 8-10ft of romex NM-2 in 1" PVC conduit for mainly protection since this was going to be exposed. Now I have some concerns after reading that I...

Can I run a power cord conduit [ 1 Answers ]

I have a residential sewage pump station in the front of my house. It’s a 300 Gallon concrete pump chamber. In it, there is a Gould (Model 3886) Submersible sewage pump with a 220v plug that gets plugged into a SJERhombus Super Single pump switch that has a piggyback plug. That plug in turn...

Do I need conduit to run a 220v cable through my cellar? [ 10 Answers ]

I'm running a 2-2/4 aluminum cable for a 220v circuit from my barn from the panel in my house. Once entering the home (from the 36" deep in-conduit run from the barn), I have to string the cable through the mechanical area (cellar) of the house, then through a center-home crawl space and then...


View more questions Search