    Is Romex allowed over concrete block?
    I have a detached building with a block foundation. On the inside, the top of the blocks is about 4" above the concrete floor. The walls are aligned with the outside of the 8" wide block therefore there is a 4" wide shelf (top of the blocks) that runs along the perimeter of the building. I used this shelf to run all wiring as opposed to drill holes in the stud. I thought, if need be I will place something in between the concrete block and the wire bundle to better protect the wire. This chase will be closed with a baseboard (side and top) so that the wire bundle will be more than 1 1/4" away from any nailing surface, so I am hoping there will not be a need to install a metal plate of any sort.

    Well it is time to get ready for inspection (I am not required to have one done but thought it be a good idea for insurance purposes). So the question to the collective is, Do I need something in between the Romex and the concrete? If I do will the foam seal (used under exterier walls and comes in a roll) work?

    Regards,

    Imran Malik
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Feb 21, 2006, 04:56 PM
    We will get to the Romex vs. Concrete Block later.

    You need to be careful bundling Romex, or any cable for that matter, long distances, due to the possibility of heat in the bundle caused by electric loads.

    As you collect cables you need to know how many of each cable is a current carrying wire, and the bundle will be subjected to derating factors as per code as the quantity rises. As 4-6 wires= 80% of ampacity, 7-9=70%, 10-20=50%.

    You usually need to use the next size wire, in general, for all the cables. This gets expensive.

    Many inpectors frown on the practice of bundling cables and consider it a low budget method.

    As far as the Rx on the block, as long as the block is dry, and the cables are protected from nails, screws, etc. then no problem.
    Imran Malik's Avatar
    Imran Malik Posts: 2, Reputation: 1
    New Member
     
    #3

    Feb 22, 2006, 07:06 AM
    Tkrussel,

    Thanks for the quick feedback. I will verify the maximum # of wires but believe there are no more than 3 or 4. Also they are not tied in a bundle as I was concerned about heat. The confined space would endup being 4" x 2" after baseboards, perhaps I can increase that to 4" x 4" because that space is not really usable.

    Regards,

    Imran

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Installing a french door in concrete block [ 3 Answers ]

I’m thinking about installing a new French door in by basement. My question is what is the best way to attaché to the door to the concrete block? Should I cut the opening to the required rough opening size and attach the door directly to the block. Or should I make the opening larger, and frame the...

Romex through cold air return? [ 3 Answers ]

Is it allowable to pull romex from attic (second floor ceiling light) to the basement through the cold air return?

Am I allowed half of his tax return? [ 2 Answers ]

My spouse and I have been separated for 3 months. I recently filed his tax return online for him, at his request, and he wanted it direct deposited into my account. He told me he would give me 600.00 of it, although he is getting 1800.00 back. Due to some very violent behavior a couple of days...

Why is this allowed? [ 7 Answers ]

There are reports that once the rescue of people is done, the National Guard has orders to shoot any stray animal on site. Animals are starving. They swim to rescue boats and are being turned away because the boats are for people, yet the rescuers for animals are not allowed to rescue them. ...

Error Message - Column Not Allowed Here [ 3 Answers ]

I tried to create a table and got the following message: COLUMN NOT ALLOWED HERE. What is the solution for this? Regards MATHEW


View more questions Search