    Replacing 2 prong receptale with 3 prong with no ground wire
    Was wondering how to replace a 2 prong receptacle with a 3 prong one. There is no ground wire running to the box and it is housed in a metal box. The receptacle is downstairs, where I plug in my dj equipment. The house is an older house built iin the 60's.
    ebaines's Avatar
    ebaines Posts: 12,131, Reputation: 1307
    Expert
     
    #2

    Feb 7, 2011, 09:58 AM

    The best way to do this is to replace the old 2-hole receptacle with a Ground Fault Circiut Interupter (GFCI) style of receptacle. Here are some quick instructions:
    How to - Install a GFCI Outlet
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Feb 7, 2011, 10:09 AM
    Keep in mind, using a GFI will offer protection from a ground fault, however, it does not create an equipment ground, and any equipment that must have a solid equipment ground to operate, such as a surge suppressor, will not operate properly.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #4

    Feb 7, 2011, 12:03 PM
    If you need a proper way to fix this circuit you need to run a new cable from the service panel to the receptacle.

    Depending on on the amperage of the circuit (14/2 AWG for 15 amp. 12/2 AWG for a 20 amp circuit)and an equipment grounding conductor. If you are using NM (Romex) cable, the EGC is included inside the cable sheath.

    A GFCI receptacle does no provide a grounded outlet as indicated by TK.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

In a 2 prong to 3 prong adapter is the ground needed? [ 3 Answers ]

I had someone install a game port connected to a power inverter in my car. The game port ended up being a 2 prong outlet. I need to connect a 3 prong plug to it an have an simple adapter but I was wondering if the ground is really needed in this case and what would be the result if I didn't...

What do I do with the white wire when converting a 4-prong dryer cord to a 3-prong? [ 2 Answers ]

I moved into an older house and have a brand new Maytag Bravos dryer. I took the 4 prong cord off and there is a white wire that was installed under the middle prong of the 4 prong cord. The white wire is part of the dryer... it comes from a bunch of wires inside the dryer. I am now putting a 3...

Changing 2 prong electrical receptacles without a ground to three prong with ground [ 1 Answers ]

How can I change all the two prong receptacles without a ground mounted in plastic outlets boxes to 3 prong receptacles with ground ?

Replacing 2-prong receptacle with 3-Prong -NO GROUND WIRE [ 6 Answers ]

Hi there! I was wondering if someone can tell me how exactly I go about doing this safely. I have an existing 2 prong ungrounded plug... theres no ground to this receptacle... old metal box does not seem to be grounded either. I would like to replace this receptacle with a 3 prong GFCI...


View more questions Search