    Pulling wire through conduit
    I have to pull 3, #4's and 1, #8 (150' ea.) through 1 1/2" PVC. There are 2, 90 degree bends. Am I better off to pull 1 or 2 wires at a time, with a additional pull rope, or just pull all 4 at one time. I have plenty of lubricant available.

    Comments? Suggestions?

    Thanks
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #2

    Jan 4, 2008, 11:24 PM
    Pull them all together
    biggsie's Avatar
    biggsie Posts: 1,267, Reputation: 125
    Ultra Member
     
    #3

    Jan 4, 2008, 11:54 PM
    I have pulled many cables as an Electrician for a power company

    And agree with Washington1 -- they make a pulling sock that is like

    The Chinese finger puzzle that grips cable for pulling... Usually best

    To have someone feeding and keeping wire straight -- and someone

    Pulling -- a pipe or long bar can increase pulling power when pulling

    Rope is wrapped around it and leverage gives more pulling power...

    One of the biggest mistakes I saw was wadding wires in a knot at end--

    Best to taper cables like the tail of a snake-- taping ends at different

    Locations --stagered --- Really pulls much easier
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #4

    Jan 5, 2008, 07:37 AM
    A Fish tape, is usually pushed through the conduit, Attach wires with Head(where wires attach to fish tape or rope) and try to keep smaller than all conductors. You can use the chinese grip if available. You can also use a vacuum to pull a string or line to use to pull with a rope. Basically, just because you MAY not have Fish Tape, or the chinese grip, doesn't mean it can't be pulled.
    Also, leave enough wire at each end(If the Panel is 1 foot x 2 foot(height+width), have 3 foot for connecting)
    If you know exactly where and how to connect, the wires can be shorter.
    Rover88's Avatar
    Rover88 Posts: 68, Reputation: 14
    Junior Member
     
    #5

    Jan 5, 2008, 10:42 AM
    These guys are all right. If you're using a pulling sock, you can also use a swivel between the sock and the rope to keep your cables from knitting. We ALWAYS pull an extra piece of jet line into the conduit for future use.

    biggsie, I wish I could get all of our guys to understand tapering the end of for the pull!
    drs72's Avatar
    drs72 Posts: 21, Reputation: 1
    New Member
     
    #6

    Jan 5, 2008, 12:12 PM
    This went much easier that I had expected. I stripped back the insulation about a foot on each wire. I removed about half of the strands from each. I then folded them back to form a loop and wrapped the wires back over themselves.

    I used braided 3/8" nylon rope to pull with. I looped this through the wire loop and used some of the single strands of copper the wrap around the 2 pieces of rope that formed the loop. I then wrapped everything with electrical tape.

    I had a helper that pushed and lubed the 4 wires while I pulled. It took about an hour of prep time to layout the wires across the yard and prepare the loop. It only took about 20 minutes to actually pull the bundle through. I think the wire lube really made the difference.

    I stressed over this much more than I should have. Thanks for everyone's help.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #7

    Jan 5, 2008, 04:16 PM
    Good Deal, If you do a lot of this, you will want to strip less than a foot, in case other end needs it, then the short pieces left over can go between meter and disconnect.
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #8

    Jan 5, 2008, 08:16 PM
    I see no reason why it wouldn't have been easy in your case. You sized the conduit larger than required (Smart move).
    drs72's Avatar
    drs72 Posts: 21, Reputation: 1
    New Member
     
    #9

    Jan 7, 2008, 06:04 AM
    Yeah, I was planning on 1" conduit, which would have probably been sufficient, but the cost difference to go to 1 1/2" wasn't that much. I'm sure glad I spent the extra money.

    The only thing I regret not doing, and I always have in the past, is run an extra pull string for future use. Just got on a hurry and forgot to do it. I sucked the first one through with a shop vac. Not sure if this trick would work well with wires present.

    Thanks for all of the help.
    DuginMT's Avatar
    DuginMT Posts: 1, Reputation: 1
    New Member
     
    #10

    Jun 20, 2012, 10:23 PM
    Pulled five 10ga THHN's today through 80' of buried 3/4" PVC conduit with two 90 Degree bends. My pull rope was 3/16" cotton clothesline. I put five loops in the end of the clothesline about 2" apart apiece and hooked each wire in each loop with about a 2" bend back on each wire, without wrapping the wire around itself. Then taped the whole run with electrical tape. Some of the taped knots were over 1/2" diameter which made for a firm pull - estimate about 25 lbs of force average. My wife fed the wire in one end while I pulled. It didn't take long to get it through though and I now have permanent power to my two story shed/playhouse. Hope I didn't saw completely through the elbows!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Can you use Metal Conduit as ground to convert 2 wire to 3 wire? [ 3 Answers ]

I need to convert an old cinder block house from 2 wire outlets to 3 wire by adding a ground to all outlets. Since the entire house is cinder block, all the circuits from the basement breaker box are in flexible metal conduit and metal outlet boxes... Is it possible to use the metal conduit...

Two-wire conduit grounding [ 1 Answers ]

My new furnace has metal box with an electrical plug and switch on the side. Three-wire conduit (with black, white and green wires) runs from that box up to an overhead light with a metal box. An older piece of two-wire conduit (with black and white wires) runs from the light to the breaker box. ...

Proper wire and conduit size? [ 2 Answers ]

Hi, I have just had a new pole building built. I had a 200 amp service installed. I will be installing 16 fluorescent light units. I will install them on at least 2, possibly 3 circuits. My question is what is the formula for figuring out the proper wire size, and how many of these conductors can I...

UF wire and copper propane line in same conduit [ 1 Answers ]

Is it safe and allowed to run 10/3 UF electric cable and 1/2" copper tubing for propane in the same 2" PVC conduit 18" underground from a house to a garage?

Pulling wire through conduit [ 2 Answers ]