    Proper grounding for 400A service and adjoining panel
    I am installing a 400A service panel on the outside wall of a garage. For the time being it will only be supplying power to a 125A panel located on the inside wall of that garage. The 125A panel will be mounted inside the wall directly behind the 400A service, and the two will be connected by means of a nipple through the back of each panel.

    My question is this: Do I treat the 125A panel as a subpanel and float the neutral? Also, for the EGC, do I run it from the 400A panel and then use a bonding jumper to the 125A? For the nipple, since I'm using a steel close nipple, do I need to use grounding lockrings?

    I appreciate your help, I've looked through my NEC and even broke out my NEC handbook. Thanks again.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Sep 22, 2007, 03:23 AM
    What you don't state exactly is the location of the main breaker.

    I will assume it is in the 400 amp panel.

    For the 125 amp subpanel, does not matter, this panel must be considered as a sub.

    When you say "float the neutral", you mean not bond it? Correct.

    The neutral must be kept insulated and isolated from the metal can and equipment ground. A separate equipment ground bar gets bolted directly to the metal can with machine screws, for all branch circuit equipment ground wires and the feeder ground from the main panel.

    The nipple only needs standard bushings, does not need bonding bushings. Only need to bond raceways containing service entrance conductors, for example, those from a meter to a main panel.

    The grounding electrode conductor needs to connect to the neutral bar in the enclosure that contains the main breaker, and that neutral bar needs to have the Main Bonding Jumper to the metal can.

    From this point on, all feeders need a separate equipment grounding wire.

    Hope this helps.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

200 amp service / grounding [ 3 Answers ]

I have a 200 amp meter on a power company pole in the country for barn electricity. I have built a small shed 285' away and want 100 amp service. Based on the distance, I am planning on using 4/0 4/0 2/0 Al URD cable in 2" conduit buried 24". To get the lug sizes to fit the 4/0, I am using 200...

Grounding/neutral meter box and panel [ 1 Answers ]

I'm istalling a 100 amp service in the yard w/meter for the lake equip. The pole will have 3 conductors from the power transformer to the meter box (neutral an two hots). The ground wire from the ground rod connects at the meter box at the same lugs as the neutral? Yes? Or to the meter box...

200 AMP Service panel to 200Amp Sub Panel [ 1 Answers ]

I getting new 200Amp service to surface mount service panel. I want to run 2oo cable to bring it sub panel in my Garage which is approx 120Ft Run through ceiling. 2 Questions 1. Is there any ristriction on running a 200AMP inside house to garage ? 2. I got a dirt cheap subpanel that has...

How Many Grounds Needed for a New 400A Service Entrance [ 5 Answers ]

I'm relocating and putting a new 400A meter main / service entrance (Milbank M400 feeding 2 200A subpanels) on the side of the new garage I'm building and I wanted to find out some information on what and how many grounds are needed? I've read for my area a ground connection is needed to the cold...

How do I instal a grounding rod to an older main panel ? [ 3 Answers ]

I have a friend who want me to instal a grounding rod on his home because he said that he was showering and when his electric furnace kicked on it kicked his , almost out of the tub, now He was tols that his home needed a grounding rod instaled to ground the house. Existing panel didn't have a...


View more questions Search