    Power distro unit
    I don't know if you are familiar with the company motion labs. So what I want to know is how many 15 or 20 amp breakers I can run using a 50 amp breaker as the main.
    You see what I'm trying to do is use a portable sound system in my church sancturary, and the thing is their circuit breaker panel is already full from top to bottom. If that can't work my church also has a power outlet that is mounted on the outside of the church that is used to power rv`s. please help me.
    What I'm hooking up to unit is 3 power amps one per breaker and 4 rack equipment components, 3 of the components each will be pluged in with the power amp.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Aug 25, 2009, 06:50 AM
    The issue is not how many outlets you can have on a 50 amp feeder,it is how much load a 50 amp feeder can serve.

    You can connect no more than 12,000 watts, or 6,000 per each of the two hot legs, assuming you have 120/240 volt single phase service.

    You can have as many outlets as needed, just cannot exceed 12,000 watts.

    And this assumes the show is no longer than 3 hours. If so, then the max load will be 9,600 watts, derating the 12KW by 80%.

    How do you plan to connect these outelts to the 50 amp outlet? Do you have a portable distro panelboard?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Ac power is on but unit will not come on [ 3 Answers ]

Ac power is on but unit will not come on.

New ac unit no power [ 4 Answers ]

Help! I have a brand new air conditioner and furnace and I cannot get the a/c on. I have read many sites and the problem seems to be no power to the outside unit. I have checked the breakers, but assume it hasn't been tripped as it has never been on! The other problem is that my panel is not...

Difference between a Power Distribution Unit (PDU) and a Remote Power Panel (RPP) [ 1 Answers ]

Is there any difference between a Power Distribution Unit (PDU) and a Remote Power Panel (RPP) in context of data center? If yes, then what is it?. Thanks.

401k distro or taking it as a loan? [ 3 Answers ]

Hello, I have a new job and my 401k($18k) with my prior company is still at my former company's plan admin which is also my new employer's admin! Combine income for my wife and I are in the 6 figures. Income goes to the "big"house payment and with a new baby, I am thinking of cashing my 401k...

In what order do I put the wires on the distro cap? [ 1 Answers ]

I recently gave my 88 honda civic a tune up, but I neglected to keep the wires on the old distributor to copy the order in which the wires are placed on the cap. I have the correct order from the engine, but... help! I don't want to screw that up. The wires are numbered 1-4 (no kidding). Does...


View more questions Search