    5464xanadu's Avatar
    5464xanadu Posts: 3, Reputation: 1
    New Member
     
    #1

    Dec 6, 2013, 11:11 AM
    Outlet tests good from outlet to lamp, but no light. Lamp checks out?
    I put my tester on the circuit (outlet) and it shows good. I test a lamp on another circuit (works fine) and then on the circuit I am testing. Tester follows electricity from the outlet, along the cord, right to the lamp (bulb) but the bulb will not light. Two outlets on same circuit and both will not light the lamp. I have never experienced anything like this. Can you help? I have done the usual checks (compared everything with working circuits). Can't solve it!
    creahands's Avatar
    creahands Posts: 2,854, Reputation: 195
    Ultra Member
     
    #2

    Dec 6, 2013, 11:17 AM
    Have you tried anything else in these outlets?

    Chuck
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #3

    Dec 6, 2013, 11:29 AM
    When you say "tester" do you mean one of those plug in devices or a multimeter?

    If you re using a plug in device, try a meter and let's see what the voltage level is at both receptacles.
    5464xanadu's Avatar
    5464xanadu Posts: 3, Reputation: 1
    New Member
     
    #4

    Dec 6, 2013, 11:30 AM
    Quote Originally Posted by creahands View Post
    Have you tried anything else in these outlets?

    Chuck
    Yes, I did all the logical steps such and testing several devices on several circuits to eliminate the obvious (bad device in lieu of circuit). I spent several hours troubleshooting. Been around construction over 40 years. Never saw anything like this.
    5464xanadu's Avatar
    5464xanadu Posts: 3, Reputation: 1
    New Member
     
    #5

    Dec 6, 2013, 11:40 AM
    Quote Originally Posted by donf View Post
    When you say "tester" do you mean one of those plug in devices or a multimeter?

    If you re using a plug in device, try a meter and let's see what the voltage level is at both receptacles.
    I used a Dual Range A/C voltage detector. When it finds voltage, it lights up. The brighter the light the stronger the voltage. Lights up bright just like on the good circuits but will not activate the device (lamp, etc) like the other circuits. I only use GOOD outlets that are not on same Circuit. Understand, I do a little of everything but am not a master at anything in construction (except maybe framing).
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #6

    Dec 6, 2013, 01:19 PM
    That type of tool will pick up any electrical signature if finds, not necessarily the one you are looking for.

    Use a meter and set it to 200 Vac.to test both the presence and strength of the line.
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #7

    Dec 6, 2013, 04:33 PM
    Indications are that you have a broken neutral. Pull the outlets and see if the quick connect holes in the back of the outlets were used. If so, rewire using the screw terminals. The quick connects are known to develop bad connections over time.

    The bad connection can be at the first non-working outlet or at the last working outlet on that circuit.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Should we replace our 4-lamp fluorescent fixtures with new 2-lamp or 3-lamp [ 1 Answers ]

We are replacing our 4-lamp T-12 fluorescent fixtures. One vendor suggests new 2-lamp fixtures while another tells us 2-lamps will not provide enough light and suggests 3-lamps. I want proper lighting but don't want to pay any more than necessary.

Where can I get an alien baby lamp?the xeno lamp [ 4 Answers ]

I have been looking for the alien xeno lamp for a while I really want one bad but I can find a store or online where I can find one if you know or if you have one for sale notify me and most likely ill buy it :p

Cannot Reset Lamp Timer Following New Lamp Insatllation [ 2 Answers ]

I replaced LCD lamp in my panasonic TV (pt-44lcx65). I get a message on my screen to reset timer and the lamp light on the front of the TV is still on. The replacement buld is a dlp (bp96-00224j). The instructions that came with the lamp refer me to the manual for timer reset and the manual refers...

What's the configuration for a 2 switch/2 lamp circuit where one lamp's always ON [ 8 Answers ]

Can someone tell me what is the switch and wiring configuration for a 2 switch/2 lamp circuit where one lamp is always ON? This configuration is rarely used, but it IS used, nevertheless, in small apartment buildings where there is a hallway and a long, dark stairway to the upper floor. There are...


View more questions Search