    Number of outlets and lights on one residential circuit
    I live in a town home with unfinished basement. As part of finishing my basement I am now wiring the family room. The room is almost 18' x 14' and there is one 15A dedicated circuit meant for this room. I am thinking of the following outlets to be in that circuit.

    1 GFCI
    9 regular receptacles attached to that GFCI
    1 staircase light
    1 Corridor light
    1 regular light/fan fixture (for future use, if need be)
    6 recessed lights of 6" diameter

    My question is: Is the number of outlets and lights are within the NEC guidelines?
    Any other comments are also welcome

    Thanks in advance
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jun 4, 2007, 02:58 AM
    Since there is no maximum amount of outlets for a residential circuit, the amount is fine, however, another circuit would be a good idea. Perhaps a separate circuit for all lighting?

    Once the basement is finished, the outlets will no longer need to be GFI protected.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #3

    Jun 4, 2007, 06:10 AM
    I would maybe pull a second circuit, Maybe for a heater in winter. Does it get cold there?
    Tripping 15A circuit could Possibly leave you in the dark.
    hbuilder's Avatar
    hbuilder Posts: 15, Reputation: 1
    New Member
     
    #4

    Jun 4, 2007, 10:02 AM
    My service entrance panel has vacant spaces only for two more new breakers. I am planning to use them for baseboard heating (for the basement) as a future project. Since I do not want to mess with the service entrance panel wiring I will get someone to do that later -- may be next year. I will be pulling AWG-12 wires for this purpose (one each for the family room and the bedroom) from the utility room, where all the wires get into the basement from the service panel. As the family room and bedroom are separated only by a single wall I can use AWG-12/3 and terminate them in a gang box on either side with blank covers.

    That means the existing wiring will never be used for heating (yes it does get pretty cold in Minnesota :)). My estimate was even if some one uses 50-65W bulbs for all the 6 recessed lighting and the other two. Still the total consumption would be about 500-700 W. More than that would be too much for such a room. If you guys think it is something not really recommended then I will consider alternatives before inspection. The room in fact is 16' x 14' with stairs running into the room couple of feet.

    I am wondering if 6 recessed lights would be too much for this room size.

    Thanks
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #5

    Jun 4, 2007, 12:51 PM
    It doesn't get any easier, cheaper, or less destructive than now, to run wiring for future heaters now, just cap off at box and don't connect to breaker until ready.
    Why not pull #12 and a 20 amp breaker.
    %80 of 20 Amps is 16 Amps(@120 Volts).
    16 X120=1920 Watts.
    50-65 watt bulbs is 3250 watts. 3250/120=27.0833 Amps
    More recessed would not be bad.
    6-65 watt bulbs =390 watts.
    Don't forget TV/Tel, Alarm wiring.
    If fans are even remote possibility, Run wiring and 4x4 now.
    They also make wafer type breakers(2 breakers fit in 1 spot, or are 1 breaker/2 switches)
    hbuilder's Avatar
    hbuilder Posts: 15, Reputation: 1
    New Member
     
    #6

    Jun 4, 2007, 01:23 PM
    Quote Originally Posted by Stratmando
    It doesn't get any easier, cheaper, or less destructive than now, to run wiring for future heaters now, just cap off at box and don't connect to breaker til ready.
    I am doing most of the wiring for the future heaters now itself. I will do all the required indoor wiring -- except that it won't be hooked up to the service panel.

    Quote Originally Posted by Stratmando
    If fans are even remote possibility, Run wiring and 4x4 now.
    Did that already!

    Since the wiring is almost done with 14AWG I do not want to go for 12 AWG unless it is absolutely necessary.

    Whole basement is being finished as:

    one 13x10 bed-room,
    one 16x14 family room,
    a 12x6 nook adjacent to the utility room
    and a 9x5 bath room.

    There are three different 15A circuits plus a 20A bathroom line shared with that in the upper level. All these circuits were wired by the builder and capped off in the basement to be used later while finishing the basement. The circuits are being used as following:

    1. one 15A circuit for bed-room
    2. one 15A circuit for family room.
    3. The third 15A circuit will be common to the nook (three outlets and a light), the sump pump, the bath room lighting and exhaust.
    4. 20A shared line will go to one GFCI outlet in the bath room.

    After reading the comments I am thinking of hooking up the corridor and stairwell lights also to this nook circuit for better balancing.

    Any comments on that?

    Thank you
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #7

    Jun 4, 2007, 02:01 PM
    On the stairwell, and corridor? I would wire for three way switching.
    Maybe recpticle for convience in the corridor,(Recpticle night light?).

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

How many outlets/lights/rooms/other on one circuit? [ 8 Answers ]

I have a house built in the 1890s with the original knob and tubing wiring. I'm completely remodeling the bathroom and I want to rewire 3 bedrooms. At first, my plan was to use one circuit per room, but I'm not going to have enough circuits in the existing panel for that. So my question is,...

How many outlets for one circuit [ 1 Answers ]

I am inclosing my garage and making it into a entertainment room. It has two outlets know one of them is for the garage door opener. The lights are on another circuit. I the cicuit will be running a big screen plasma TV and stereo as well as some table lights. I have bought 2/12 romex and was...

Number of outlets per braker [ 4 Answers ]

Is there a rule of thumb as to the number of outlets on a 20 amp circuit. How about a 15 amp. I do understand that 20 amp will carry about 2400 watts and 15amp will carry about 1800 but all of the outlets will not be used at the same time. This is for a residential room expansion with limited...

Wiring basement - outlets/lights per circuit [ 3 Answers ]

I'm finishing my basement and I'm getting ready to do the wiring plan. I plan to have both outlets and lights on each circuit and I'm planning on 3 circuits (1 for a workshop (20Amp?), 2 (15 Amp?)for the rest of the basement including a rec room, craft room, bathroom, closets). Are there code...

Too many outlets on a circuit? [ 5 Answers ]

My wife and I moved into our home 2 years ago(newly built) and the home had an unfinished basement(2 car garage and 2 unfinished rooms). The basement is currently on 1 circuit. Both rooms are now finished and each have 4 electrical outlets. The garage has 3 eletrical outlets, and there are also 2...


View more questions Search