    Neutral from main lug in garage
    Calling all electricians, here's what I've done. Installed main lug in detached garage. Ran 3 #3 wires and #6 ground. First went to 60 amp fusible cut off to protect panel components. Hots fit into lugs but neutral doesn't. So spliced them together with aluminum electrical splice. Drove 2 ground rods (6' apart) and tied into ground buss. Neutrals and grounds are separated and did not bond box. Now at the main panel hooked into 60 amp 2 pole breaker. However neutral does not fit in the neutral/ground buss. Does everything sound OK to this point and can I piggyback the neutral with the feed neutral under the mains neutral lug.thanks in advance for your help. D
    Handyman2007's Avatar
    Handyman2007 Posts: 988, Reputation: 73
    Senior Member
     
    #2

    Sep 1, 2013, 08:33 PM
    You through the word "lug" around like crazy. I do not understand why the neutral wire will not fit the connectors in the box. That stymies me. I would have tio see that set up to make any more comments on this. Splicing the ground (earth) is a no no... Do you have less then 25 ohms between the earth rods? Too many questions
    denman's Avatar
    denman Posts: 48, Reputation: 2
    Junior Member
     
    #3

    Sep 1, 2013, 10:14 PM
    Quote Originally Posted by Handyman2007 View Post
    You through the word "lug" around like crazy. I do not understand why the neutral wire will not fit the connectors in the box. That stymies me. I would have tio see that set up to make any more comments on this. Splicing the ground (earth) is a no no....Do you have less then 25 ohms between the earth rods?? Too many questions
    Did not splice the ground. Spliced neutral wires together, which is essentially the same as tying the feed in to the connector in cut off box and then running the neutral out to the main lug panel from the other side of the same connector. No idea why holes are too small in diameter to accommodate the # 3 wire. From all the homework I've done ,I think I'm OK at the garage but couldn't get an answer if it was all right to piggyback the neutral (that goes to garage) under the same connector as the neutral feed to the main breaker panel goes under. Sorry, I'm trying to be as informative as I can , but sometimes my explanation is a little skewed. Thanks d
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #4

    Sep 2, 2013, 04:54 AM
    Splicing the ground (earth) is a no no...
    Sometimes yes. Sometimes no.


    Do you have less then 25 ohms between the earth rods?
    And just how is a diyer supposed to check this. Do you think he has the required $1000+ tester it takes? Do you? I don't.
    Besides, he has two rods. The 25 ohm requirement goes out the window if you install two rods.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #5

    Sep 2, 2013, 04:55 AM
    however neutral does not fit in the neutral/ground buss.
    You need to find out what brand panel you have and get a forked lug, or an add-on neutral lug for the bigger wire.
    Most neutral/ground bars will take up to #4. After that you need an add-on lug.

    Do not piggy-back two wires under one lug.
    denman's Avatar
    denman Posts: 48, Reputation: 2
    Junior Member
     
    #6

    Sep 2, 2013, 06:03 AM
    Quote Originally Posted by stanfortyman View Post
    You need to find out what brand panel you have and get a forked lug, or an add-on neutral lug for the bigger wire.
    Most neutral/ground bars will take up to #4. After that you need an add-on lug.

    Do not piggy-back two wires under one lug.
    OK thanks
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #7

    Sep 2, 2013, 07:29 AM
    Why are you using #3 AWG conductors and a #6 AWG neutral. A #3 AWG conductor can handle 85 amps and a #6 AWG conductor is 55 amps.

    What is the distance from the main service panelboard to the downstream panelboard?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #8

    Sep 2, 2013, 08:04 AM
    Why are you using #3 AWG conductors and a #6 AWG neutral. A #3 AWG conductor can handle 85 amps and a #6 AWG conductor is 55 amps.
    Don. #3cu THHN is good for 100A, not 85A.
    #3NM cable is good for 85A which would typically be placed on a 90A breaker.

    Also, he said a #6 ground, not neutral. A #6 ground is actually oversized for this feeder. A #8cu ground would have been fine.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #9

    Sep 2, 2013, 09:58 AM
    No where in the original post or subsequent posts is the type of wire discussed.

    Nor is there any reason to believe that the panelboards or the fusible cut-off switch are listed for 90(C).

    Which means to me that if the poster is using a listed 90(C) conductors, then the only reason to use them is for adjustment and correction purposes.

    So, if they are listed 90(C) conductors they still can only be used as if they were in the 60(C) column which equals 85 amps.

    Of course using the 80% load on the breaker this would allow up to 65 amps. Hey that answered my question! :)

    Denman, what type conductors are you using?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #10

    Sep 2, 2013, 11:05 AM
    No where in the original post or subsequent posts is the type of wire discussed.
    When was the last time you saw #3 NM cable?


    Nor is there any reason to believe that the panelboards or the fusible cut-off switch are listed for 90(C).

    Which means to me that if the poster is using a listed 90(C) conductors, then the only reason to use them is for adjustment and correction purposes.

    So, if they are listed 90(C) conductors they still can only be used as if they were in the 60(C) column which equals 85 amps.
    Who said anything about 90 deg C?
    #3cu THHN in conduit with normal 75 deg C terminations is rated for 100A in the 75 deg C column or T310.15(B)(16) of the 2011 NEC.


    Of course using the 80% load on the breaker this would allow up to 65 amps.
    What rules is this? A breaker can be loaded to 100%.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #11

    Sep 3, 2013, 04:58 AM
    I must be having a brain dead moment Stan. Again, I come back to the fact that the poster has not indicated the listed connections of either the service panelboard or the disconnect switch in the garage.

    without that information we can only use the 60(C) column. Also, if the conduit is to be installed underground, then THHN cannot be used because it is not listed for Wet areas.

    Actually, I was using the 2014 (Pre-Release) edition of the NEC and I am not disputing the amperage of the wire. I am disputing the fact that without the proper listing information we cannot make the leap to the full value of the 90(C) listing.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #12

    Sep 3, 2013, 04:46 PM
    I must be having a brain dead moment Stan. Again, I come back to the fact that the poster has not indicated the listed connections of either the service panelboard or the disconnect switch in the garage.

    Without that information we can only use the 60(C) column.
    I haven't seen a 60 deg C termination in years. Most are 75 deg C with a few 90 deg as well. To assume terminations or breakers are 60 deg C is 1970's or 80's thinking.



    Also, if the conduit is to be installed underground, then THHN cannot be used because it is not listed for Wet areas.
    Probably for the 1,000,000th time... pretty much all new(er) THHN is dual rated THWN.
    This correction does not have to be made any more.
    denman's Avatar
    denman Posts: 48, Reputation: 2
    Junior Member
     
    #13

    Sep 5, 2013, 05:31 AM
    I'll have to get back to you on that. The work is at my nephews place. Can't get back there till Sun. You guys are talking way above my head, but I'm a fan of reading your posts back and forth.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #14

    Sep 6, 2013, 03:55 AM
    Denman,

    On the inside of the metal boxes for both the panelboard and switch there should be information stamped into the metal. The name of the manufacturer, and within that data should be the "Listed" information. This will tell you whether the terminals of the switch and panelboard are listed for use up to 75(C) or limited to 60(C).

    If both devices are listed at 75(C), then we can use the higher of the two amperages when selecting the cable. However if one is listed for 60(C) then we must select the cable from the 60(C) amperages.

    I expect the panelboard to be listed at 75(C), it's the switch that is the unknown.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Main lug panel with a 60 amp main breaker [ 2 Answers ]

I have main lug panel in my home with a 60 amp main breaker in it being used for the main feed of the panel, the main lugs are being feed from the meter box to the panel with 2- 2/0 and a concentric neutral looks to me like a 100 amp service cable . Can I install a new 100amp or 125 amp panel on...

Difference between Main Lug and Main Breaker Panel [ 8 Answers ]

What is the difference between a Main Breaker Panel and a Main Lug Panel and can either be used in new residential construction.

Load Center Main Lug or Main Breaker for the Attic [ 5 Answers ]

I have a large attic (on 3rd floor), 38'x28', which is unfinished space. The 2nd floor central air-condition is located there and used to be fed by a 60 feet of 12/3 cable (I changed the cable to 10/3 to reduce the chance of voltage drop) and it's fed by a dual 15A breaker (240v breaker) in the...