    Minimum rigid conduit size
    What is the minimum conduit size for 3 -#2 copper wires to a service panel?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Oct 22, 2009, 01:26 PM
    Always needs to know the insulation, as different types have different outside dimensions.

    Assuming THHN/THWN insulation, 1 inch is the minimum.

    Electricians never use 1 in GRC for 3 #2 wires. We will always use a min of 1-1/4".

    Just the way we are.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #3

    Oct 22, 2009, 01:47 PM

    Might you need 4 wires. L1, L2, G and N?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire size & conduit size for 60 am subpanel 150 from source [ 9 Answers ]

Indiana question: I want to install a 60amp subpanel 150 feet from the main panel. This is all exposed runs both inside and out in a commercial envirenement. What gauge and type of copper wire and what size conduit whould I use. How often should insert a junction box in the run. John

What size conduit? [ 1 Answers ]

Hello. I've already run underground about 50' of 3/4" conduit but have to pull out existing cable and replace with new cable. New cables will be: three #6 cables, one #8 and four #12's. I know it can be fished through but not sure if its code acceptable. I expect to upgrade my service panel some...

Conduit size [ 3 Answers ]

What is the minimum diameter grey pvc pipe for the following direct burial cable? Aluminum 4/0 2/0 4/0 urd? Aluminum 1/0 2/0 1/0 urd? Can I run a #4 copper ground wire in the conduit with the urd cables Thanks

Minimum vent size [ 1 Answers ]

I am installing a full master bath away and inaccessible to the vent stack. I am using a 3" drain(PVC) for toilet, sink and shower. What is the minimum size vent stack I should use?

How to size Conduit 6-3 [ 4 Answers ]

I have 2 6-3 for a 60ft run and 1 6-3 for another run. Question, what size conduit do I use. This circuit is for a tankless water heater. All will in my garage which is drywalled.


View more questions Search