    Max Amps in a Panel and adding a sub panel for more circuits
    Hello all,

    I recently moved into a condo with a 200 amp panel (in my unit). The main panel is in the electrical room of the building and my unit was previously a commercial retail space.

    I did some remodeling and my panel is now full. The total combined amps of all the circuit breakers currently in the panel is 445 amps. During the remodel, there were no more than 3 or 4 20 amp breakers installed (the rest were pre-exsisting).

    Question 1) Am I completely over capacity of my panel? And do I need to reduce some of the circuit breaker ratings? Or what needs to be done to make it "safer"

    Question 2) I am looking to upgrade the wiring for a home theater system and to do so, I will need at least another 50 amps or so. Can this be accomplished by adding a sub panel to my main? Or is the 200 amp rating for any and all power ultimately running current through the panel?

    What can I do to get the additional 50 amps needed for the home theater?

    Thanks!
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    May 2, 2008, 04:20 AM
    Adding up the rating of the breakers is a completely useless number. It means NOTHING.

    I assume you are doing this as well with the H-T? 50 amps is a LOT even for a decent H-T.

    Install your sub-panel and you are fine. You can move some circuits over to the new sub to make room in the main panel.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #3

    May 2, 2008, 07:53 AM
    A word of caution, you must be a licensed electrician to work on wiring or panel in a condo. I'm sure the NEC does not give any wiggle room on that particular mandate.

    Did you get a permit for any of the electrical work you have completed so far?
    x-tnsiv's Avatar
    x-tnsiv Posts: 2, Reputation: 1
    New Member
     
    #4

    May 2, 2008, 08:41 AM
    Quote Originally Posted by stanfortyman
    Adding up the rating of the breakers is a completely useless number. It means NOTHING.

    I assume you are doing this as well with the H-T? 50 amps is a LOT even for a decent H-T.

    Install your sub-panel and you are fine. You can move some circuits over to the new sub to make room in the main panel.
    I might just take out of my singles and install duplexes now.




    Quote Originally Posted by donf
    A word of caution, you must be a licensed electrician to work on wiring or panel in a condo. I'm sure the NEC does not give any wiggle room on that particular mandate.

    Did you get a permit for any of the electrical work you have completed so far?
    I have a licensed electrician that is going to be doing the work. I just couldn't get a hold of him to ask the proper questions.

    But thanks for the help!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Max Circuits in a Sub Panel [ 8 Answers ]

I have a 100A sub panel in my attached garage that is fed with 6/3 (copper NM-B) off a 40A breaker in my main panel. The panel has 6 slots and will handle 12 circuits. Now, my understanding is as long as I don't have more than 6 circuits on this sub panel, I am not required to run the feed...

Determining capacity and maximum circuits in panel [ 1 Answers ]

I can't find this info anywhere. I can only assume it's a dumb question. When I look at my 100 amp panel I see 32 spots for breakers. Down one side I count 16 and another 16 on the other. There are two 30 amp and 1 60 amp, and then about 20 more 20 amp breakers. When I add it up I get 510 amps....

Adding Sub-panel and moving existing circuits to it. [ 1 Answers ]

I'm looking at getting some tools that will require having 220 for them. My main panel is full right now and has several Slim/Tandem/double breakers in it already. Reading some things on the net I see that the panel might be exceeding the limit it should have for breakers, but don't know at this...

Sub panel circuits [ 1 Answers ]

I Want to replace an existing unused 20 amp two phase electrical outlet with a sub-panel containing single phase 110 volt circuits with appropriate circuit breakers. My question is: How many separate circuits does the NEC allow in this type of sub-panel?

Sub panel fed with two circuits [ 3 Answers ]

I was looking for space to add a circuit to an existing sub panel at my mother's house and ran into a problem that I need some advice on. Upon opening the sub panel, I discovered that it is being fed with two 12-3 Romex wires originating from two 20A circuits at the main. Now, I think that I...


View more questions Search