    Looking Wire a generator 4 #2's and 4 #18's what size PVC pipe is required ?
    Looking Wire a generator 4 #2's and 4 #18's what size PVC pipe is required ?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Nov 9, 2011, 06:13 AM
    What are the #18 wires for?
    Wired1's Avatar
    Wired1 Posts: 2, Reputation: 1
    New Member
     
    #3

    Nov 9, 2011, 06:27 AM
    Two communication and two for battery charger
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Nov 9, 2011, 12:05 PM
    #18 is not allowed to be used as a building wire, the charging circuit is 120 volts and will need to be a min of #14.

    The communcation cannot be in the same conduit as the power.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #5

    Nov 9, 2011, 02:20 PM
    TK, many generators, such as Generac, do allow the control wiring in the same conduit provided it is a limited length of run.
    The control wiring is typically a 240v reference signal that tells the genny that the utility is on, and the other is the load side of a battery charge circuit coming from the transfer switch.

    I will say though, #18ga seems small to me. I would not use smaller than #14.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #6

    Nov 10, 2011, 03:29 AM
    Control is one thing, communication is another. All I can go by is the information provided.

    Perhaps Wired1 can provide more details of what is being done.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

PVC pipe size [ 1 Answers ]

What size PVC pipe do I need to put 3 #6 and 1 #8 wire in?

Wrapping required to the pvc pipe contact with concrete [ 2 Answers ]

Should all pvc pipes/ non-metallic pipes required wrapping when they are embedded in retaining/ concrete wall

Size of wire required for 70 amp boxservice [ 3 Answers ]

I am installing a 70 amp outdoor box, one 30 amp 220v and two 20 amp 110v breakers for a travel trailer. The meter loop is rated at 125 amp. I am running this service from the meter loop, main box under ground to the 70amp outdoor box. WHAT SIZE WIRE WILL I NEED TO USE, the total run from end to...

Pvc pipe size per code [ 1 Answers ]

I have a 1982 double wide cavco that sits above ground. I had a slow drainage problem in the tub and shower. I called the plumber out, actually three of them worked on the issue, and was not resolved. The supervisor explained that after trying for four hours, they were going to call it quits. He...


View more questions Search