    dean1234's Avatar
    dean1234 Posts: 9, Reputation: 1
    New Member
     
    #1

    Jan 15, 2010, 07:51 AM
    Load calculation
    How is the load for a sub-panel calculated? I had asked this in another post but never found an answer. This for a laundry room with a 240 volt /30 amp dryer and two 20 amp 120 volt ckt and one 15 amp 120 volt ckt. The feed line is apox. 25 feet. What size breaker should I install in the main panel?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jan 15, 2010, 12:37 PM
    Bare minimum size feeder will be a 60 amp breaker using #6 copper wire.

    I would run #2 aluminum wire and protect the new panel with a 100 Amp breaker.
    dean1234's Avatar
    dean1234 Posts: 9, Reputation: 1
    New Member
     
    #3

    Jan 15, 2010, 02:16 PM
    Quote Originally Posted by tkrussell View Post
    Bare minimum size feeder will be a 60 amp breaker using #6 copper wire.

    I would run #2 aluminum wire and protect the new panel with a 100 Amp breaker.
    If I used # 6 copper, can I use # 8 copper for a neutral?

    What type of wire( covering )and what would the size of the conduit be?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Jan 15, 2010, 02:23 PM
    Use #6 for the neutral. The wire can be THHN/THWN in 1 inch conduit. You will also need a #10 green for the equipment ground in addition to the three #6's.

    Be sure it keep the neutral insulated and isolated at the panel, and use an equipment ground bar bolted directly to the metal box of the panel using machine thread screws, for all bare or green equipment grounds

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Load Calculation [ 2 Answers ]

I am currently reviewing estimates on replacing a split gas furnace and ac unit. The ac is a 3ton Tempstar, but was originally 2.5 ton (unknown brand/model). I replaced the ac last summer with a used 10SEER 3ton I found for sale locally online to get us through the year since I was contemplating...

Load calculation [ 0 Answers ]

How do I estimate the size of the solar appliance that will support the load in a goven building?

Load Calculation [ 9 Answers ]

I have a 100 amp switchbox.The left side has 6 slots ( 1 double switch 20amp, 1 double bar 30amp and 2 single 20amp. The right side has 3 double switch midgets at 20amps and 2 single 20amps. My question is how much can my box take and how do I calculate the usage?

Load calculation [ 1 Answers ]

There is a indoor pool and normally water is heated to temp 40 deg c. Total water quantity is 15000 ltrs. Out door temp is 44 deg c. The indoor a/c results in high amount of condensataion in supply grilles. FCUs are used to cool the area with 10% of fresh air. There is no possibility of untreated...

Load calculation [ 2 Answers ]

Respected sir I amprakash ihave doubt regarding load calculation. I have a 5 amp socket (ups power ) .can I connect 5 computors to that socket through extension box.please explain me any body knows


View more questions Search