Lighting and Outlet Circuits
Can lighting and receptacles be on the same circuit or should they be on separate circuits?
|
|
 |
New Member
|
|
Jan 31, 2007, 10:49 PM
|
|
Yes they can one 15 amp circuit can have no more than 10 outlets or switch legs on it not a problem this is for a home dwelling yes ?
|
|
 |
Uber Member
|
|
Feb 1, 2007, 04:04 AM
|
|
Depends on th location of these circuits. Kitchen counter,appliance and dining room outlet circuits can only have outlets, no lighting can be on them. Also, a circuit that handles outlets in mulitple bathrooms can have no lighting.
Otherwise, general purpose lighting circuits can have both lighting and receptacles on thoise circuits.
Having a mix of lighting and outlets or having more than one circuit in one room can have benefits thou. If one circuit has a problem, the other circuit can supply power and lights while the other circuit is repaired.
Having lighting separate from outlets will prevent large applainces from causing the lights to flicker.
|
|
 |
New Member
|
|
Feb 1, 2007, 11:04 AM
|
|
 Originally Posted by tkrussell
Depends on th location of these circuits. Kitchen counter,appliance and dining room outlet circuits can only have outlets, no lighting can be on them. Also, a circuit that handles outlets in mulitple bathrooms can have no lighting.
Otherwise, general purpose lighting circuits can have both lighting and receptacles on thoise circuits.
Having a mix of lighting and outlets or having more than one circuit in one room can have benefits thou. If one circuit has a problem, the other circuit can supply power and lights while the other circuit is repaired.
Having lighting separate from outlets will prevent large applainces from causing the lights to flicker.
The bathroom is gfi. Kitchen & dining room yea the Q was for like I basic room everybody knows you have to split the room. "code"
|
|
 |
New Member
|
|
Feb 1, 2007, 03:05 PM
|
|
 Originally Posted by Hoot01
Can lighting and receptacles be on the same circuit or should they be on separate circuits?
Thanks... This is for general purpose lighting and outlets.
tkrussell your answer brought up another question or two though. You said that "a circuit that handles multiple bathrooms can have no lighting."
1) Can a bathroom have all lighting, exhaust fan, and outlets on one 20amp circuit.
And
2) If I supply the outlets for two bathrooms with one 20amp circuit can I then use adjoining bedrooms circuits (20amp) to supply lights and exhausts fans for the bathrooms. I know that I still have to stay within the 80% rule for these circuits.
|
|
 |
Uber Member
|
|
Feb 1, 2007, 04:00 PM
|
|
 Originally Posted by Hoot01
1) Can a bathroom have all lighting, exhaust fan, and outlets on one 20amp circuit.
Yes, only if that circuit is for that bathroom outlet, fan, and lights.
 Originally Posted by Hoot01
2) If I supply the outlets for two bathrooms with one 20amp circuit can I then use adjoining bedrooms circuits (20amp) to supply lights and exhausts fans for the bathrooms. I know that I still have to stay within the 80% rule for these circuits.
Yes, exactly.
|
|
 |
New Member
|
|
Feb 3, 2007, 09:47 AM
|
|
Thanks again.
|
|
Question Tools |
Search this Question |
|
|
Add your answer here.
Check out some similar questions!
Circuits
[ 2 Answers ]
Suppose that the switch has been closed for a length of time sufficiently long for the capacitor to become fully charged. (a) Find the steady-state current in each resistor. R1=16.00 kΩ, R2=12.00 kΩ, and R3=2.00 kΩ. (b) find the charge on the capacitor. 9.00V, 10.0uC
I found part (a) but I'm...
Must you re-wire outlet to outlet?
[ 8 Answers ]
Hi there. Great site.
I am rewiring my 1950's house with plaster walls, older wiring had no ground. Because it is one story, and extremely tight in the attic on the outer walls, I ran a 12/2 home run for the outlets, to a big (1900?) junction box, then "spidered" out to each individual...
Sub panel circuits
[ 1 Answers ]
I Want to replace an existing unused 20 amp two phase electrical outlet with a sub-panel containing single phase 110 volt circuits with appropriate circuit breakers. My question is: How many separate circuits does the NEC allow in this type of sub-panel?
120 volt outlet from 240 volt outlet
[ 1 Answers ]
I understand that it is possbile to wire a 120 volt outlet from a 240 volt outlet. My 240 volt outlet has 3 wires in, white, black, and a ground. Do I wire the 120 volt outlet from the either wire and the ground? My voltage meter indicates that connection is 120 volts. Is there any down side to...
Circuits in Kitchen
[ 6 Answers ]
I just replaced my appliances in my kitchen and when installing the Fridge they had to plug it in to a different outlet from before. I didn't think it should share an outlet - but I looked at my circuit box and there doesn't seem to be a dedicated Fridge outlet. The electric range is on it's own...
View more questions
Search
|