    Light Bulbs Blowing Regularly
    The lights in our house keep blowing, even after bulbs have been replaced. It takes weeks or months, but it is getting crazy. First a bulb or two in the ceiling fan, then the attic, the bathroom light, then both of the upstairs hallway lights at separate times, then the back porch light, and now an entire strand of white lights used for decoration. This has happened in under a year's time. What could be the cause?
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #2

    Apr 7, 2008, 06:39 AM
    A loose Neutral(white wire) will cause voltages to go High and Low, since it effects the whole house, I would have all Neutral connections checked from power company through meter and to Electrical Panel. I would tighten hots and grounds while things are open.
    Jeff Beck's Avatar
    Jeff Beck Posts: 3, Reputation: 2
    New Member
     
    #3

    Apr 7, 2008, 08:49 AM
    Due to the wide spread nature of your problem, I would agree with the previous post. However I'll put my two cents worth in for others that may have a similar problem with just a couple locations that seem to have a short life. I had a Bathroom and a closet bulb that seemed to have an extremely short life. They were close to my A/C Air handler. I concluded the vibration from the unit was more than the filament of the bulb could take. I replaced them with compact fluorescent and they haven't been changed since.
    ceilingfanrepair's Avatar
    ceilingfanrepair Posts: 5,733, Reputation: 109
    Uber Member
     
    #4

    Apr 7, 2008, 10:22 AM
    Neutral issue, higher-than-normal supply voltage, or frequent power surges.
    eric34's Avatar
    eric34 Posts: 56, Reputation: 1
    Junior Member
     
    #5

    Apr 8, 2008, 10:37 AM
    If the fixture is old. The tab for the hot in the socket can be to far from the bulb. Turn the power off... pull the tab tward the bulb
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #6

    Apr 8, 2008, 12:30 PM
    Vibration is a primary killer of light bulbs.

    Light bulbs also have the nerve of all dying at about the same time.

    And the one that's harder to figure out is a bad manufacturer's lot.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #7

    Apr 8, 2008, 12:41 PM
    Since it it happening everywhere, I think finding neutral problem is better solution than
    Installing 130 Volt Rough Service Bulbs. Normally they never see 130 volts, and running at 120 volts they last longer. May be a solution. Do you ever see brights get bright or dim at times(more than usual variation?)

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Light bulbs keep blowing out too soon [ 18 Answers ]

I have two outside security lights; one by the front door and one by the side door. I am having to replace the bulbs in them about every 2 weeks. I've tried different wattages and even different brands/quality of bulbs. Same thing. Two or three weeks then POOF! Blow out. Power surge possible? Fire...

My light bulbs keep blowing out [ 23 Answers ]

Hi. The light bulbs in my kitchen and dining area keep blowing out. I hired an electrician to do some other work, and he said my bulbs just blew. However, after I purchased new bulbs, they still blew out. Some of the bulbs are halogen and others are incandescent. I don't have any problems with...

Specialty bulbs blowing [ 6 Answers ]

We've already assessed that in this apartment, we are getting about 124 volts at the box. I've had a big problem with regular incandescents blowing, but will soon be replacing them with 130v bulbs (as soon as the current 120v ones burn out). So that problem should be solved. However, my...

Ceiling fan light bulbs blowing out [ 5 Answers ]

In our living room, the ceiling fan has four light bulbs, and we need to replace them at least every 4 weeks or so. They are 40 watt, 120 volt lights. They always blow out when they are NOT on. I've heard it quite a few times - during the day when we don't need the light on, you can hear the...

Halogen Track Light blowing bulbs [ 1 Answers ]

I added a third light (one that had been sitting in my closet for years) to one of my tracks which immediately blew the bulbs in the other two lights. Thinking the light to be defective, or perhaps the limit on the track to be 2 not 3, I removed it and replaced the bulbs in the other two lights....


View more questions Search