    L530 Generator outlet to L1430 Transfer Switch inlet
    My problem is similar to https://www.askmehelpdesk.com/electr...et-391704.html but I cannot see what the final resolution was.

    Here are my specifics:
    I have a Yamaha EF2800I inverter generator with an L530 female output receptacle. My home has a GenTran 3028K 30 Amp 8-Circuit Transfer Switch. The transfer switch has an L1430 male inlet on it.

    Hooked up to the transfer switch are the following (all 15 amp breakers):
    2 fridges
    1 pellet stove
    1 living room lights circuit
    1 hallway lights circuit
    (the generator has run all these at the same time off extension cords in the past)

    I'd like to use the transfer switch and avoid my extension cord mess, but since I want the low noise rating of the inverter generator, I'm faced with either figuring out how to hook an L530 outlet to an L1430 inlet or spending $3000 on an inverter generator that has the L1430 outlet.

    I feel like I'm making too many assumptions here and I need some help.
    I *think* I could do the following:
    1) buy an L530 male inlet plug
    2) remove the L1430 male inlet from the transfer switch box
    3) wire nut the red and black wires from the transfer switch together with a third jumper
    4) connect the white and green from the transfer switch to the L530 as directed
    5) connect the jumper to the third remaining blade on the L530

    I know this will not support running my well pump during a power outage. I understand that I'll need to put the L1430 male plug back and buy a bigger generator if I want to do that someday. I'm concerned that the loads will not be split evenly when they get to the transfer switch and are connected to the red and black wires.
    sundaymtn's Avatar
    sundaymtn Posts: 2, Reputation: 1
    New Member
     
    #2

    Nov 4, 2009, 09:12 AM

    Here's what I'm going to try. The transfer switch came with a cord (L1430 male and female). The female end plugs into the transfer switch nicely so I'll leave that as is. The male end does not plug into the generator so I'm going to replace it with a L530 male that does.
    To connect the L530 to the cord I'll jump the two hots to the single hot connection on the L530, then ground to green, neutral to silver.

    With this set up I'll only be supplying 120 to the house so I will not be able to connect any 120/240 appliances to the transfer switch panel. That's OK since I'll only be running the few things listed above.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Connecting a 240 volt 20 amp duplex outlet on a generator to a 20 amp transfer switch [ 1 Answers ]

I have an older Coleman generator (5 KW) that a 240 Volt duplex outlet 20 AMP. I have a transfer switch rated for 5 KW that has a twist lock connector. How do I make a cord to go from my generator to the transfer switch without having to re-wire my generator? Thanks, Stan

30 amp generator installed to a 60 amp transfer switch? [ 7 Answers ]

THis is the generator I want to install, 6800 Watt Portable Genearator ELECTRIC START # Wattage * Running Watts: 6800 Watts * Maximum Watts: 8500 Watts my plan is to mount a box on the outside of the house, with the 120-240V L14-30R inlet, so I can plug a extension cord if I...

Generator transfer switch [ 1 Answers ]

How difficult is it to install a generator transfer switch? It's pre-wired, doesn't look too Difficult. Is there anything I should look out for? The only thing I'm not sure of is it comes with two 15-amp 1-pole breakers, two 20-amp 1-pole breakers, and one 2-pole 20 amp breaker. How do I tell the...

Generator transfer switch - enough for well pump [ 1 Answers ]

I have a 10hp 5600 generator that I want to connect to a "GenTran 20216 Manual Transfer Switch". It states that this transfer switch has 6 switches (rated 15 amps ea), a handle tie for one 2-pole circuit such as a well pump. My question is this - my well pump is 220 30 amps. Does two switches at...

Transfer Switch & Generator Compatibilty [ 3 Answers ]

I have installed a manual transfer switch in my home. It says in the instructions to make sure the neutral is un-bonded to the generator. My Generator has a bonded neutral to the frame. What can I do to make the switch and the Generator compatible? Thanks


View more questions Search