    Junction Box size
    I have and oven with 10/3 mc cable attached. I am going to splice this to a 10/3 romex cable that I pulled from the sub panel. Is a metal 3" deep single gang box big enough? How many cubic inches do I need?

    Thank you
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Apr 19, 2006, 02:07 AM
    Need to allow 2.5 cubic in for each insulated #10 wire, and 1-2.5CI for all grounds.
    6- #10 x 2.5 CI= 15 + 2.5 for the grounds=17.5 cubic inch minimum

    A 4"x4"x3" box has 48 CI of space ,so the box is fine
    loupi01's Avatar
    loupi01 Posts: 92, Reputation: 1
    Junior Member
     
    #3

    Apr 19, 2006, 07:24 AM
    tkrussell,
    Again, many thanks for your help.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Junction box question [ 2 Answers ]

Hello. I have a quick junction box question. Is there a limitation to the amount of wires I can safely join in a junction box? If so, what is it and are there regulations to what size box I can use? Thank you. I would like the have 8 wires (neglecting ground) in one junction box (1 in / 3 out)....

Size of dog [ 2 Answers ]

My 6 month old labX weighs 50 pounds and only goes up to about my knee, the vet at 4 months told us she'd be roughly 90 pounds (her dad was 120), her mom was only 60 pounds, will she grow any taller? She isn't overweight, nice and sleek looking, she eats about 4 1/2 cups of food a day and is very...

Right Size? [ 5 Answers ]

Hi, Has anyone tried right size? It's some kind of weight loss smoothy or drink or something. I was wondering if anyone has tried it, how it tasted, and if it worked? Thanks...


View more questions Search