    Installing a ground rod
    I have 220 on my dock and only 3 wires are in the box. Red, White, and Black. They drove a ground rod in on the bank. We want to add 110 v light and recept. I know how to come off one leg fro the power but being that they did not run a ground from the main panel, am I to use the wire from the ground rod as my ground for the 110?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Jun 28, 2010, 11:44 AM

    What does "I have 220 on my dock" mean?
    A panel? Just a circuit?

    If this is a panel as I suspect you have an older 3-wire feeder. The ground rod does not provide anything as far as the circuits go. The neutral will be bonded on the panel and serves as both neutral and ground. The ground rod is also required by code but serves other purposes.

    Can you post a picture of the box or panel at the dock?
    Without that it is impossible to tell what it is you have there.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Nec-covering of ground wire from the ground rod to the water pipecables [ 1 Answers ]

I installed a new service meter panel and ground rod. The ground rod is connected to the meter panel via a #4 copper wire to a water pipe located 10 feet away. Is is allowable to bury the #4 wire between the ground rod and water pipe to keep it from being a trip hazard and protect the wire? ...

Ground rod wire is not connected to the ground rod [ 1 Answers ]

My inspection report for a property that I'm looking to purchase said that my " ground rod wire is not connected to the ground rod". I have no idea what something this would cost to fix. He also said that the ground rod clamp was rotten. Am I looking at thousands in repairs?

Ground rod instead of ground wire? [ 7 Answers ]

I'd like to install an RV outlet (120v, 30amp) in our parking area. Unfortunately, I only have two wires available to that location and adding a third wire would be quite difficult. Can I use the two available wires for hot and neutral and drive in a grounding rod next to the outlet for the...

Ground Rod / ground wire [ 9 Answers ]

Hello, I am installing a 100 amp subpanel in my workshop 125' away from my house. I have two ground rods in the ground by the shop, and was wondering if it was necessary to run 4 wires from the house to the shop (two hots, one neutral, one ground), or could I just run the three wires from the...

Ground Rod Installation [ 4 Answers ]

I am installing a concrete patio 20'x18' over the area where the ground rod is currently installed. If I relocate the ground rod, what is the maximun distance from the main panel can the ground rod be installed?


View more questions Search