    How many 100 Amp sub panels can be added to a 200 Amp Panel
    I have a 7500 sq ft home, it requires a 200 amp main, I have three floors and was wondering how many sub panels could I run off a 200 amp main?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Oct 5, 2012, 07:20 AM
    I fixed the title, you had watts when you meant amps.

    You may have as many loadcenters (AKA subpanels) fed by the Main Panel as desired.

    For a 3 story structure, one per floor would suffice, and assuming the Main Panel is in the basement, that would give you a panel per level for those branch circuits on each floor.

    Has a service rating load calculation been done, to determine if a 200 Amp service is adequate for this home?

    My gut tells me it is not. But calculations would tell.

    Just for lighting alone at 3 watts per square foot is 93 amps, less any applicable derating factors. Add appliances, heat, air conditioning, unless everything is gas, 200 amps is not enough.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Oct 5, 2012, 07:06 PM
    I agree with TK. I find it hard to believe that the load calc is under 200A.

    Is this home under construction?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Updating service panel to 200 amp with feeder to 100 amp panel in old house [ 8 Answers ]

I currently in the process of converting 1000 sq ft of attached garage into living space while doing this we are updating electrical service to 200 amp new service, there is 100 amp service in the old part of the house which will remain but need to be sub paneled from the new 200 amp service. I...

Running two 100 amp main panels from a 200 amp service [ 27 Answers ]

Greetings! I live in a rural country area. The electric company will be installing a pole, meter, and 200amp service with disconnect at pole. (It will require 50 foot run of service cable from pole to main load center in mobile). Currently the double wide has a General Electric 100amp Main...

Running two 100 amp main panels from a 200 amp service single lug meter [ 1 Answers ]

I have a 200 amp meter with single load side lugs. Presently my house is tied to these lugs. I'm building a remote garage which will require a 100amp feed. Tieing the house to the garage is not doable due to the location of the driveway. I would like to have the existing 200 amp meter feed...

100 amp main, 100 amp service wire, 200 amp sub panel? [ 2 Answers ]

I am moving my sub panel and upgrading to a 200 amp service, but in phases. The first phase is to move the panel due to some remodeling. I want to put a 200 amp panel in the laundry room with a 200 amp breaker. I have 100 amp feeder wire going to it (AL 2/2/2). Outside I have the meter can and...

200 amp service to 2 100 amp sub panels [ 9 Answers ]

I have a 200 amp meter main From it I want to run 2 100 amp sub panels about 150' in distance for each I want to be able to draw max amps from each at any given time My plan is to use direct burial type wire and run both wires leaving meter main inside one 2" conduit riser - to 2...


View more questions Search