Ask Experts Questions for FREE Help !
Ask
    shadowx360's Avatar
    shadowx360 Posts: 7, Reputation: 2
    New Member
     
    #1

    Jul 9, 2008, 09:23 AM
    How Double Pole Circuit Breaker Trip?
    On my electrical service panel, the "MAIN" breaker is a double pole breaker and each side is marked "100 Amps." Does that mean that when the total amperage exceed 100 one side it will trip, or if the total of both sides exceed 100 amps it will trip? Also, I recently bought a new electric range. I need a double pole breaker because it uses 240 volts, and the total consumption of the range should not exceed 40 amps. Should I get a double pole breaker with 20 amps marked on each side (the whole thing is marked 20 amp double pole breaker) or should I get one with 40 amps marked on each side (the whole thing is marked 40 amp double pole breaker)?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Jul 9, 2008, 09:55 AM
    240 V is really two 120 volt sources 180 degrees out of phase with one end connected to ground. In order to pro

    Tect the load, both sources of 120 need to be removed. The breaker trips when either side exeeds 100 A. If the load was a water heater, both breakers would see the same current. If on side shorted to ground, then one side would be exceeded. In 4-wire 240 volt installations where a neutral is involved, the currents would be different.

    You have a 100 amp main breaker.

    Current consumption and required breaker may be two different things. You need a 40 A double-pole breaker (40 A on both sides).
    shadowx360's Avatar
    shadowx360 Posts: 7, Reputation: 2
    New Member
     
    #3

    Jul 9, 2008, 10:47 AM
    Quote Originally Posted by KeepItSimpleStupid
    240 V is really two 120 volt sources 180 degrees out of phase with one end connected to ground. In order to pro

    tect the load, both sources of 120 need to be removed. The breaker trips when either side exeeds 100 A. If the load was a water heater, both breakers would see the same current. If on side shorted to ground, then one side would be exceeded. In 4-wire 240 volt installations where a neutral is involved, the currents would be different.

    You have a 100 amp main breaker.

    Current consumption and required breaker may be two different things. You need a 40 A double-pole breaker (40 A on both sides).
    So if both sides of my main breaker were allowing 99 amps to pass through (total of 198 amps), then it will not trip, and will trip if one side has 101 A passing through it and the other has 50 A passing through?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #4

    Jul 9, 2008, 10:53 AM
    In theory, yes. The tripping time would be different depending on the amount of overload. Meaning a 100 A breaker would trip faster at 150 A than 101 Amps.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #5

    Jul 9, 2008, 05:24 PM
    Quote Originally Posted by shadowx360
    So if both sides of my main breaker were allowing 99 amps to pass thru (total of 198 amps), then it will not trip, and will trip if one side has 101 A passing thru it and the other has 50 A passing thru?
    Just to clarify. We do NOT add up amperage in a 120/240v service to get the equivalent 120v current.
    For instance, it is not accurate to say a 100A service is the same as 200A at 120v. This is incorrect, even for comparison reasons. It is 100A @ 240v, or 100A on each of two legs of the service.
    This is NOT the typical case of 1+1=2. 100A + 100A does not equal 200A.


    Also, KISS makes a very good point about trip curves. A 100A breaker will likely never trip at 101A.
    It can sit at 110A for several minutes and longer. It can be at 150A for quite a few seconds. It will trip instantly at a 20,000A fault.
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #6

    Jul 9, 2008, 06:28 PM
    KISS: I like that. Wow you guys must have a very close relationship> :D
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #7

    Jul 9, 2008, 06:43 PM
    You've never heard that acronym before? "The KISS method"?
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #8

    Jul 9, 2008, 08:52 PM
    Quote Originally Posted by stanfortyman
    You've never heard that acronym before? "The KISS method"?
    No, never heard of it. Yet I have seen the name: KeepItSimpleStupid
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #9

    Jul 9, 2008, 09:02 PM
    How about the SWAG method?
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #10

    Jul 10, 2008, 09:32 AM
    Quote Originally Posted by KeepItSimpleStupid
    How about the SWAG method?
    Yes, I heard of it! Sop. Wild---Guess

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

30 Amp Double Pole Breaker is hot and tripping [ 10 Answers ]

Hi, I just got a Maytag Neptune Dryer a week ago. I have it plugged in to our old dryer outlet (which was replaced less than a year ago) which is 3 prong. The dryer voltage is 240 volts and I am running it on a 30 amp double pole breaker. The problem is, this is new electrical wiring and a...

Using a Double Pole Breaker to feed two circuits [ 11 Answers ]

I have 40' run from the main panel with BX and want to use 14/3 instead of two runs of 14/2. Is there a problem using a double pole breaker (15amp) to feed (with 14/3) a split receptacle and then a lighting circuit on one half and 4 receptacles on the other? Is the only drawback is when one...

Circuit Breaker didn't Trip [ 7 Answers ]

I have a 1 year old home. The bathroom outlet is a GFCI outlet on a circuit protected by a 15 amp ARC FAULT BREAKER. Today my wife plugged her hair blowdryer and the base of the cord lit up like an arc welder. This lasted for 5-8 seconds before the cord completely melted and the fireworks...

One pole of untied double-pole circuit breaker breaks [ 5 Answers ]

I recently purchased a new dryer (220 v appliance) to replace an older model. The old dryer was connected to the panel via a double-pole breaker except that there was no clip or tie between the poles. I changed the location of the outlet when installing the new dryer, replacing the cable with the...

Circuit breaker failed to trip [ 2 Answers ]

I made a big error today on wiring a new circuit. I pulled 2 cables (for 2 circuits) back to the consumer panel and then connected the wrong cable. The cable that I connected was stripped at the other end but not yet connected to anything. When I went to inspect it, I tugged on it and there was one...


View more questions Search