    How did I determine the neutral wire?
    I have 2 wires running underground to a lamppost in my yard. I want to install a GFCI outlet in the post. To do so, I believe I have to determine which one is the neutral wire and which one is the hot wire. (Neither is colored) How can I determine which is which?
    mr500's Avatar
    mr500 Posts: 181, Reputation: 8
    Junior Member
     
    #2

    May 7, 2008, 08:57 PM
    Just 2? No grounds ?
    SC-tbfd's Avatar
    SC-tbfd Posts: 58, Reputation: 1
    Junior Member
     
    #3

    May 7, 2008, 09:10 PM
    If you have a tester, voltage is best but just a small test light should work, run an extension cord from a known properly wired outlet and test from the unknown wires to the neutral on the extension cord (that's the longer slot). You should only get voltage on the hot wire.

    As a side note I agree with mr500. Underground wire to an exterior lamp with no ground sounds like a bad thing. This lamp is 120volt right?
    gwashburn's Avatar
    gwashburn Posts: 3, Reputation: 1
    New Member
     
    #4

    May 8, 2008, 06:33 AM
    Quote Originally Posted by mr500
    Just 2? No grounds ?
    Yes, just 2 wires, there is no ground wire. It's an old house built in 1930. I've read that installing a GFCI outlet will make this lack of ground safer. That's why I'm trying to figure out which wire is the neutral wire. How do I do this?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #5

    May 8, 2008, 07:02 AM
    Exactly what was stated.

    CLARIFICATION OF THE HARD WAY

    Find a ground somewhere. If you have to, use the outside of the meter base.

    Another way is to find a properly grounded outlet if the house has been re-wired.

    You can even use a cable connection or the ground on the NID for the phone service.

    Run a wire such as an extension cord and measure the voltage between a known good ground and each of the wires. One will read 120 and the other 0. The two reading zero is neutral.

    THE SIMPLE WAY

    While writing this there is an EASY way to do this. Connect the wires to the GFCI. If the GFCI works, you have wired it correctly. If it doesn't you have wired it wrong. No damage will occur to the outlet if the polarity is wrong. Then, if you would like, you can use a simple, maybe $3.00 outlet tester to check your work.

    The GFCI should come with a label that you can use when the outlet uses no ground. Use it.
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #6

    May 8, 2008, 07:14 PM
    I agree with Keepit!
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #7

    May 9, 2008, 09:38 AM
    How about since there is no ground, and a GFCI needs ground to measure against, you need to either pull a ground wire to the fixture or, use a GFCI breaker in place of the existing breaker.

    Oops, is your electrical wiring protected by fuses of circuit breakers?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #8

    May 9, 2008, 10:12 AM
    Don:

    A GFCI DOES NOT NEED GROUND!. It measures the imbalance of hot and neutral. This is done by winding the hot conductor and neutral conduction in opposite directions of a torroidal core acting as a current transformer. Then, there is a sense winding which can very easily resolve the diference in currents.

    In reality, reverse polarity, is picked up as a grounded neutral fault. Specifics can be found here:
    http://www.national.com/ds/LM/LM1851.pdf#page=1
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #9

    May 9, 2008, 10:27 AM
    My error and I know better. I was thinking GFCI and wrote about GFI. My bad.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Neutral wire [ 3 Answers ]

I have a eone sewer box on the side of my home and I hooked up the 4/10 outdoor wire to the sewer box like it said and I have to run that to the pole, to a 30 amp breaker OK the black and white go to the breaker and the ground to the ground bar so where does the neutral go

Using the ground or (bare) wire for the neutral wire [ 2 Answers ]

I have a problem with some wiring that I ran for an outside motion light. Although the hot leg and ground wires are fine, the neutral wire is defective ( it may have gotten knicked or something). Of course, now the wiring is covered up behind a wall that I do not want to tear into if it can be...

Neutral wire is hot [ 5 Answers ]

My air conditioning quit working last night. The service man showed me that the current available to the unit was only 100 volts. He also said that the neutral wire was hot. He could not fix this because he's NOT an electrician. I'm not either but while I wait for the electrician to show up,...

Neutral wire is hot(has voltage potential like the black wire) [ 5 Answers ]

Hi, The problem started at midnight last week. One of my line in the basement is starting to have issue whenever I connect a water pump or appliances to the outlets. Before I plug the appliance in, the neutral is neutral(zero voltage), but when I plug the appliance in, the neutral is now...

Hot neutral wire [ 3 Answers ]

Half of the house, has no power. I checked everything I thought it was, but not having any luck. I checked boxes where the power is not working for loose neutral, nothing. I have checked for lost leg in panel, nothing. I have checked for loose neutrals in panel, nothing. I have also unplugged...


View more questions Search