    rojonik's Avatar
    rojonik Posts: 1, Reputation: 1
    New Member
     
    #1

    Aug 16, 2011, 05:26 PM
    HOW TO CHANGE A 20 AMP SINGLE POLE TO A GE 45 amp circuit breaker one pole?
    I have a 20 amp service in my garage and I want to plug in my camper. The camper has an inverter that says it is rated for 45 amps. I changed the breaker to a 30 amp but it keeps popping the GFI outlet. How do I convert this amperage to meet the needs of the camper?
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #2

    Aug 16, 2011, 05:42 PM

    Presumable by 20 amp service you mean you had a 20 amp breaker and 12 gauge wire. The 20 amp breaker is the largest breaker you can use with 12 gauge wire. Put the 20 amp breaker back.

    What are you trying to do with the inverter. An inverter converts DC to AC.
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #3

    Aug 16, 2011, 05:50 PM
    Changing the breaker is a bad idea unless the wire is rated for that amperage. Since it has a 20 Amp breaker we'll expect it to be 12 AWG. 30 Amp is 10AWG. Likely to cause a fire or at least melt the wiring if loaded to that capacity. However, an inverter changes AC to DC for the camper. Is this what you were expecting? A converter would change the 120AC to 12DC. The 45 Amp rating is probably for DC, not AC. Try a non GFCI circuit and see what happens, you may have a ground fault in the camper. Please put the 20 Amp breaker back!
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #4

    Aug 16, 2011, 06:06 PM

    Brian,
    An inverter changes DC to AC. A rectifier converts AC to DC. A transformer steps voltage up or down. You are correct however that we have no idea what the voltage of the 45 amps is.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #5

    Aug 16, 2011, 06:29 PM
    Quote Originally Posted by rojonik View Post
    I have a 20 amp service in my garage and I want to plug in my camper. The camper has an inverter that says it is rated for 45 amps. I changed the breaker to a 30 amp but it keeps popping the GFI outlet.
    I'm sorry, but this is what scares me about folks attempting to do electrical work when they have absolutely no idea what they are doing. :(


    Quote Originally Posted by rojonik View Post
    How do I convert this amperage to meet the needs of the camper?
    You need to run a new line to the location, properly sized for the load.
    Can you tell us what the plug is on the camper cord?

    WHAT is rated at 45 amps? Inverters are typically rated in wattage, not amperage.
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #6

    Aug 16, 2011, 07:06 PM
    Hank, I know that, must have been a senior moment when I was posting!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Do single pole breakers hook black to breaker and neutral & grd to bonded neutral bar [ 6 Answers ]

I have an Eaton Cutler-Hammer meter/breaker box. (MB816B200BTS-FLCH) I want to run a 20 amp circuit (underground wire) from this box through existing underground conduit to a receptacle for a dishwasher. This run would be app. 15' to 20' and from my main house panel it would be 40' to 50'. All...

600 amp service with a 200 amp single pole breaker [ 0 Answers ]

I have a 600 amp GE service closet in my basement that feeds 7 other socket meters and each have there own breaker. Question is I just added a brands new 200 amp panel and new line service to a area I just converted to storefront space for a deli. So I can't find a 200 amp breaker for that closet...

30 AMP Tri-pole breaker [ 2 Answers ]

I'm rewiring sections of our house and need an extra slot in the panel. The dryer is wired to a tri-pole 30 AMP breaker. I have never seen this before and was wondering if I can swith it out for a 2-Pole breaker. There are three wires coming from the dryer - Red and Black to the breaker and...

One pole of untied double-pole circuit breaker breaks [ 5 Answers ]

I recently purchased a new dryer (220 v appliance) to replace an older model. The old dryer was connected to the panel via a double-pole breaker except that there was no clip or tie between the poles. I changed the location of the outlet when installing the new dryer, replacing the cable with the...

Trying to change a single pole light switch to a single pole swith with a light below [ 5 Answers ]

I have a kitchen light and a basement light that are together in one electrical box, but are on single switches. I purchased a "single pole switch and pilot light" combination so I could see easily if the basement light is on. In the box there is a black, red and white wire. For the single pole...


View more questions Search