    sawtooth111's Avatar
    sawtooth111 Posts: 4, Reputation: 1
    New Member
     
    #1

    Apr 5, 2008, 03:55 PM
    How to add and back feed a main breaker in a small convertible panel.
    I have a SquareD Q08-16L100RB Panel that I want to convert to use as a temporary on a construction site but it needs a main breaker installed. It currently has no main breaker but SquareD says you can install a "back-fed" main breaker and a retaining clip. Does back-fed mean that the line power from the meter is fed back through the main breaker to the bus? Does it mean that I install the two hot cables from the meter to the lugs on the main breaker instead of the lugs mounted in the panel that connect to the hot bus?

    Regards, Michael
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Apr 5, 2008, 05:39 PM
    Back feeding means that the output of a breaker is used as the input to a panel.

    Many times this is done with an interlock kit so that the main and the back-fed breaker cannot be on at the same time. This is for generator applications.

    If there is no main breaker, then any breaker could be used to feed a panel. Should be labeled as such.
    sawtooth111's Avatar
    sawtooth111 Posts: 4, Reputation: 1
    New Member
     
    #3

    Apr 5, 2008, 07:41 PM
    I am still not clear on the wiring, would you please edify? Was I correct that I would place a 100 amp breaker in the first position and attach the 2 hot wires from the meter to the 2 terminals on this (main) breaker?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #4

    Apr 5, 2008, 08:09 PM
    Yep. Technically the (main) breaker could be in any position. The first position makes the most sense.
    sawtooth111's Avatar
    sawtooth111 Posts: 4, Reputation: 1
    New Member
     
    #5

    Apr 5, 2008, 08:13 PM
    Wow that was fast. Does this mean that current can always flow both ways through a breaker?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #6

    Apr 6, 2008, 05:23 AM
    Well AC voltage in the US reverses polarity 60 times per second. That's one way of saying yes.

    Breakers are essentially thermal (heaters) devices with a latching mechanism. Heat typically unlatches the breaker. Heaters don't care which way the current flows. A little hydraulics in the breaker changes how the breaker responds to an overload (trip time vs. overcurrent).

    DC breakers don't care either.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #7

    Apr 7, 2008, 07:49 AM
    Correct if I am wrong, I am thinking you want to backfeed a breaker, not a panel, In this case, The wires feeding your new panel Hook to a breaker(load side of breaker),
    When this breaker is on, it energizes the Panel. The retaining clip(s) is so if breaker is pulled out of panel and is ON, the exposed breaker connections will not shock you if contact is made.
    sawtooth111's Avatar
    sawtooth111 Posts: 4, Reputation: 1
    New Member
     
    #8

    Apr 7, 2008, 08:07 AM
    Yes you are correct. Thank you for your assistance as well. The whole thing keeps getting clearer :)

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Difference between Main Lug and Main Breaker Panel [ 8 Answers ]

What is the difference between a Main Breaker Panel and a Main Lug Panel and can either be used in new residential construction.

How do you shut off and turn back on main breaker in your home? [ 6 Answers ]

How do you shut off the main breaker in your home, and turn it back on.

How to add 300 a subpanel to 2oo a main panel [ 4 Answers ]

How do you add a 300a subpanel from a 200 a main panel to install tankless water heater

Breaker size in main panel to support sub panel? [ 7 Answers ]

Hello, I am wiring a sub-panel to the outside of my home (50 feet from main 200 amp box). I ran 3 wire - 6 gauge. What is the largest 2 pole breaker I can put in the main panel to supply the sub-panel. TYPE NM-B 6-3 WITH GROUND 600 VOLTS CIRTEX-I EZ-STRIP (R) PLUS 17:11 2/5/07 SB/RC ...

Main breaker panel [ 1 Answers ]

Hi, I'm looking for a 100 or 125 amp 30 or 32 space main breaker panel(not a mlo) and have been unable to find one. Can some one tell me where I can get one with the main installed? Thanks Jim


View more questions Search