    How to add 110 circuit breaker or new sub panel
    I bought a 120v 2000 watt hot water heater. This calls for a 25 amp breaker. I only have 1 free 15 amp. Would it be better to replace the breaker or put in a subpanel? I also have my stove connected to a double 30 amp 220. Which route would be best, and could someone explain in detail how to do it. I understand all about cutting the main and the danger of current still in main wires.
    Thanks,
    Sheri
    creahands's Avatar
    creahands Posts: 2,854, Reputation: 195
    Ultra Member
     
    #2

    Jun 5, 2009, 06:50 PM

    What do u mean ''have 1 free 15 amp''?

    Chuck
    sherihonda's Avatar
    sherihonda Posts: 2, Reputation: 1
    New Member
     
    #3

    Jun 6, 2009, 06:40 AM
    I'm sorry, my mistake. It is actually a double pole 30 amp 220 breaker.
    creahands's Avatar
    creahands Posts: 2,854, Reputation: 195
    Ultra Member
     
    #4

    Jun 6, 2009, 11:19 AM

    Uhave a double pole 30amp/220 breaker not in use?

    Chuck
    ohb0b's Avatar
    ohb0b Posts: 215, Reputation: 14
    Full Member
     
    #5

    Jun 6, 2009, 11:36 AM
    Quote Originally Posted by sherihonda View Post
    I bought a 120v 2000 watt hot water heater. This calls for a 25 amp breaker. I only have 1 free 15 amp. Would it be better to replace the breaker or put in a subpanel? I also have my stove connected to a double 30 amp 220. Which route would be best, and could someone explain in detail how to do it. I understand all about cutting the main and the danger of current still in main wires.
    Thanks,
    Sheri

    You may remove the spare 15 amp single pole breaker and install a 25 amp breaker.

    The breakers are "stabbed" into the bus (held by spring loaded clamps) You just pull to remove.

    Most home improvement stores have service panel displays. You can practice removing and installing the breaker at the store.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #6

    Jun 6, 2009, 11:38 AM
    Sheri,

    Just from your minimal discussion I suspect that you are not used to working with electricity.

    How did you determine that the water heater needs 25 amps? Please read the metal label on the back of the heater to get the voltage, amperage or wattage needed by the water heater.

    You can calculate the correct amperage by dividing the wattage (2000) by the Voltage (120) to get amperage. 2000/120=16.6 amps. Because this is a water heater, the amperage must be multiplied by 1.25%. The heater would be defined as a constant on device, that means you would need the breaker sized for 16.6 * 1.25% = 21 amps. That's the reason you would need a 25 amp breaker.

    Next you would have to get the correct cable for the circuit. This means that you would have to look for a cable that can carry 21 amps. To safley carry 21 amps, ypo must use #10 AWG cable. You may use either a 25 mp breaker or a 30 amp breaker for this circuit.

    Now, as to how you would do this, that's a different story.

    If you already have a spare 15 amp circuit, then you would need to replace the 15 amp breaker with a 25 amp breaker. Then you would need to replace the 14 AWG cable from the breaker to the where you want the heater to be installed with 10 AWG.

    Under no circumstances can you leave a 14 AWG cable (listed for 15 amps) in a 21 amp circuit. It is a very real fire hazard!!!

    Please take a moment and verify the circuit requirements and get back to us. One other item, it is my very strong suggestion that you file for an electrical permit and then have the work inspected to make sure that it is up code level for you area.

    As an alternate plan, may I suggest that you contact several local "Licensed" electricians and have them bid on the job. Working on the main panel can get you very dead if your have no experience working on electrical circuits.

    P.S. As to the stove's 30 amp circuit. According to the NEC code, this is an independent circuit and as such, you cannot connect any other electrical device to it.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Replacing fuse box with Circuit breaker panel [ 3 Answers ]

I want to replace an old fuse box with a circuit breaker panel. Do I need a 200 AMP service? (considering putting in air conditioning in the future). The house has two apartments so I want to make sure there is adequate service. As I know absolutely nothing about this, what questions should I...

Adding 50 amp circuit breaker to electrical panel [ 3 Answers ]

Is there any sequence to adding a 50 amp breaker to an electrical panel. My panel has several 50 amps at the top then some 20 amps, etc. I want to add the new 50 amp breaker to the bottom of the panel after the 20 amps. Does it matter that the new 50 amp breaker is below smaller amp breaker and...

Fuse box to circuit breaker panel [ 4 Answers ]

I would like to know how should it cost to have a fuse box containing 8 fuse to a circuit panel. That fuse box is in a coop apt.

Additional Circuit Breaker panel [ 1 Answers ]

My home has a 100 amp panel, all provided circuits are now full, I want to add a hot tub circuit (approximately 45 feet from main panel) of course I'll need to install an additional auxiliary panel to accommodate the hot tub circuit. What is the best way to power this auxiliary circuit breaker...

Panel Circuit Breaker [ 3 Answers ]

I live in a four bedroom colonial. The Pacific Electrical Panel is 125amps and 29 circuit breakers of which 3 are not in use. Is it necessary to upgrade the system to 200 amps? I have no problems with it and is seldom overloaded. If I choose to upgrade the panel what is the cost of such a project.


View more questions Search