    Grounding/Bonding Backup Generator with Transfer Switch
    Grounding question for the electrical pros out there.

    I recently bought and installed a backup generator, and wired it to my main panel via a transfer switch. The system is hardwired with a power inlet box on the outside of my house.

    I have loads balanced between the two phases pretty evenly. It's been tested and is feeding properly whether on utility or generator for lights, fridge, etc. I haven't yet run my furnace on the generator, but I don't see any reason for it to be different.

    I want to make sure that I understand the neutral and grounding requirements for the generator outside so that someone doesn't get hurt standing in snow or wet grass while it's running outside.

    Generator is a Husky 3,750-Watt, Model #30438 (http://www.homedepot.com/buy/electrical/alternative-energy-solutions/husky/generator-3750-watt-77063.html)
    Transfer switch is a Gen-Tran Model #3028 30A, 7500 Watt capacity. (http://www.gen-tran.com/eshop/10Expand.asp?ProductCode=3028)
    Power inlet box installed outside the house is Gen-Tran Model #14302, 30A, 7500 Watt (http://www.gen-tran.com/eshop/10Expand.asp?ProductCode=14302)
    Wire configuration on generator and power inlet box is L14-30, run with 10/4 wire throughout.

    The transfer switch has a separate neutral bar, 1 neutral connected to neutral bar in my main panel, 1 neutral from the generator inlet.
    Transfer switch also has a separate ground lug, same thing - 1 ground going into my ground bar in the main panel, the other coming from the generator wire.

    I have 2 questions, kind of related to eachother:
    1.Neutral - this setup means that the neutral is still connected to the utility even when running on generator. Does this pose a risk of backfeeding any stray voltage and do I need to add a switched neutral kit to it?
    2. Ground - Since the neutrals are connected, do I need to disable the generator frame ground and use a separate grounding rod outside where the generator will be running?

    Thanks for the help.
    Ian
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Aug 31, 2011, 01:38 PM
    First of all, I really appreciate the detail you provided to explain your question, well done.

    You do not need to change anything, you have connected the neutral and grounding properly.

    You do not need a switching neutral. That is for specific purposes that does not apply to this typical installation.

    Be sure to test your furnace on generator well before you need it.

    Some furnaces use electronic controllers that do not work well with generator power for some reason I am not sure about.
    BigRed1500's Avatar
    BigRed1500 Posts: 70, Reputation: 8
    Junior Member
     
    #3

    Sep 1, 2011, 06:41 AM
    Thanks. So outside, for the generator itself, I do not need to add a separate grounding rod?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Sep 1, 2011, 07:06 AM
    Not needed per Code, only if the manufacturer requires a ground rod.
    BigRed1500's Avatar
    BigRed1500 Posts: 70, Reputation: 8
    Junior Member
     
    #5

    Sep 1, 2011, 07:54 AM
    Great, thanks again for the info.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Generator Transfer Switch Install [ 7 Answers ]

I live in south Florida and have a typical home built in 2005 with a 200A service which is fed through the bacck of the meter housing into the breaker box inside the garage. Or I should say, was fed that way. Last year I decided to put in a transfer switch so I could properly hook up my generator...

400amp/2-220amp grounding w/backup generator [ 1 Answers ]

I am installing a 400A. Service which will split into 2-200A panels. One will service a workshop and another will service our home. Each will have a service disconnect prior to the individual panels. The home has a 18kW backup generator. My questions are: How are the neutrals and grounds to be...

Generator transfer switch [ 1 Answers ]

How difficult is it to install a generator transfer switch? It's pre-wired, doesn't look too Difficult. Is there anything I should look out for? The only thing I'm not sure of is it comes with two 15-amp 1-pole breakers, two 20-amp 1-pole breakers, and one 2-pole 20 amp breaker. How do I tell the...

Generator transfer switch - enough for well pump [ 1 Answers ]

I have a 10hp 5600 generator that I want to connect to a "GenTran 20216 Manual Transfer Switch". It states that this transfer switch has 6 switches (rated 15 amps ea), a handle tie for one 2-pole circuit such as a well pump. My question is this - my well pump is 220 30 amps. Does two switches at...

Generator power transfer switch [ 1 Answers ]

Our power goes off on a frequent basis. If it is off more than 8 hr I need to power up with my own generator 8kw, to prevent spoilage and to run the well. My question is do you have to disconnect the neutral also and run the neutral to the generator or can the neutral be common to both power...


View more questions Search