Not your question?
Ask your question
View similar questions
Add your answer here.Check out some similar questions!
Misuse of ground wire as neutral return wire in old house
[ 5 Answers ]
Here a problem where the "obvious" solution scares me, need some advice on how to best proceed. My home (built 1920 with knob and tube type wiring) has been upgraded over the years by prior owners, but in many place still has active current in the old wires, in other places it is spliced into a...
Pulling wire through conduit
[ 9 Answers ]
I have to pull 3, #4's and 1, #8 (150' ea.) through 1 1/2" PVC. There are 2, 90 degree bends. Am I better off to pull 1 or 2 wires at a time, with a additional pull rope, or just pull all 4 at one time. I have plenty of lubricant available. Comments? Suggestions? Thanks
Can you use Metal Conduit as ground to convert 2 wire to 3 wire?
[ 3 Answers ]
I need to convert an old cinder block house from 2 wire outlets to 3 wire by adding a ground to all outlets. Since the entire house is cinder block, all the circuits from the basement breaker box are in flexible metal conduit and metal outlet boxes... Is it possible to use the metal conduit...
Conduit type and ground?
[ 1 Answers ]
I am installing a spa and will be running a 220v/50A circuit for its use. Before pouring a slab I would like to bury the conduit and stub it up at the appropriate location. What type of conduit should I use? Is it best to use solid pipe which I would need a tube bender, or can I use PVC or...
Pulling wire through conduit
[ 2 Answers ]
I currently have 100' of 10/2 UF cable running underground through 3/4" PVC conduit. I need to pull the 10/2 out, and pull in 10/3 UF (or its code equivalent) to replace it. I have 3 questions: 1) Is 10/3 UF cable always produced in a flat configuration, or does some company manufacture a round... View more questions Search
|