    Ground and neutral bar
    I'm installing a 4 wire, 50 AMP GFCI for my hot tub. My question is at my main breaker for the house where I'm taking power from, which bar is neutral and which bar is ground, or does it matter?

    Thanks

    Fred
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jul 28, 2006, 09:28 AM
    If the main breaker is in the panel that you will install the hot tub circuit breaker, both the neutral bar and equipment ground bar are connected together.

    So you probably both whites and grounds mixed on each bar. Does not matter which you use.

    In the case, for consistency, we will usually use the neutral bar that has the main neutal conducotr connected to for all the brach circuit neutrals, and the equipment bar for the greens and bare grounds, but again does not matter.

    But, if, for example you have a main panel, but the main breaker is outside, then the neutral bar is isolated and insulated from the equipment bar.

    Hope this helps.
    mascifm's Avatar
    mascifm Posts: 2, Reputation: 1
    New Member
     
    #3

    Jul 30, 2006, 08:19 AM
    It did, thanks.

    Hooked dit up and all works well.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Neutral Wire is Hot [ 11 Answers ]

I have problem with on one of the electrical outlet in my house. The problem is this, I measured from (Neutral to Ground 120V, Hot to Ground 0V and Hot to Neutral 120V). The power on this outlet will shutdown If I plug a coffee maker, radio Ect... into this outlet. Can you please advice what...

Grounding Bar vs. Neutral Bar? [ 14 Answers ]

Hello all. I have extended the wires from an unused 240 outlet to the backyard for a spa via a sub-panel. I also hooked up a new grounding electrode near it to avoid having to run a fourth wire all the way back to the main panel. This fourth wire goes to the small grounding bar in the sub-panel...

Hot neutral [ 6 Answers ]

Very confused as to way the breaker does not trip if I have a hot neutral. We had a heated water bowl for the houses and the water beencame live. 110 to the neutral.So way did the breaker not trip. Stan

Open Neutral [ 2 Answers ]

I need some expert assistance... I think that I have an open neutral on the power company's side. They came out to look at it today and didn't fix anything, and I would like someone else to evaluate my conclusion before I call them tomorrow. This is a commercial building that I am...

Using Neutral as a Ground ? [ 3 Answers ]

In my new apartment there are some wall outlets that are two prong outlets. Also my fear is that the three prong outlets are not “physically” connected to ground. I heard somewhere that in this kind of system the neutral wire can also be used as a ground. Is this correct? Would a separate...


View more questions Search