    GFCI breakers when circuit lacks a ground wire.
    Greetings,
    My home, built in the early 1950's, is wired with a 2 wire conducter lacking the ground wire. I believe it is 14 ga. My question is , would installing GFCI breakers provide protection from shock and fire, or would a more costly repair be in store?

    Thanks Sparky,

    Timashinkle
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Dec 8, 2007, 01:54 PM
    Using a GFI breaker or receptacle is allowed to protect a circuit with no equipment ground, and it will protect from shock and ground fault short circuits.

    GFI devices do not protect from line to neutral short circuits, but that is where a breaker picks up.

    Where ever possible or practical, rewire as many circuits as possible over to 3 wire, for a better quality job, but not required by code.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

GFCI outlets and breakers [ 2 Answers ]

I am remodeling a basement and the power going down comes off a split pole 20 amp breaker with 12/2 wire. I was told I need to install a GFCI. Is it possible to install 1 in the first outlet and the other 5 in line thereafter will be protected as well or would it be better to reeplace the breaker...

Under ground wire [ 6 Answers ]

Hi, I'm new to this so thank you in advance for any and all advice. I live in Massachusetts and I want to run some wire under ground from my house to a shed and a gazebo in my back yard. I'm planning on building a water garden next to the gazebo and need electricity for the pump. It's a long way...

GFCI for Permanent Above Ground Pool [ 3 Answers ]

I am looking to add an outdoor receptacle for my soon to be installed above ground pool. Obviously I want it to be a grounded outlet (GFCI)... Do I need to install an GFCI breaker ? Or can I add a GFCI outlet off an existing GFCI outlet and run it out to the pool area. I have already gone...

Ground wire [ 1 Answers ]

At what point do you have to use a ground wire in lu of metal conduit, Or do you?


View more questions Search