    Generator wiring: new generator gfci breaker tripping
    Generator wiring: I have a new honda generator. I ran 3 wires from the garage to the transfer switch in the house. When I start up and throw in the breaker on the generator, its GFCI trips immediately. It is a long run (125ft) run to the house and I used heavy wires. But I only ran 3 (blk, red, white). I connected the green to another grounding conductor between the house and the garage. Is this what is wrong? What else could it be?
    Missouri Bound's Avatar
    Missouri Bound Posts: 1,532, Reputation: 94
    Ultra Member
     
    #2

    May 14, 2010, 02:35 PM
    The connection from the generator to the transfer switch needs to be 4 wire.
    That being said, what is amperage of your generator, and what do you consider heavy wires? That's a long run.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #3

    May 14, 2010, 05:36 PM

    You also need to break the ground-neutral bond at the generator.
    There has to be only one point where the ground and neutral are bonded. You have two points. The generator and the house.

    Being 125' away, I'd install a ground rod at the generator for safety.

    And I'd also run an insulated ground.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

GFCI Breaker Tripping on Coast Spa [ 4 Answers ]

Hi, I am having a problem with my Coast Platinum Series Spa bought in 2001. The GFIC breaker is tripping. Spa information: Coast Platinum Series Model – ML40 Serial number – 004629 Control Pack/Circuit Board - TSPA-1-P122-P222-B1-01-CP1-H34.5-JJM-FL-RL-CC23453-01C Two Monster Flow 7.0...

1 phase generator with a 40 amp breaker [ 4 Answers ]

I'm connecting a 8 circuit single phase panel to a 120/240v 3wire generator. Coming from the panel I'm using a 3 conductor cable to be connected to a 40 amp breaker on the generator. My question is where does the neutral get connected at the generator

I require for a Power Plus 5000 Generator 1 generator under following specifications: [ 1 Answers ]

I require for a Power Plus 5000 Generator 1 generator under following specifications: 5000 Watts, 120V, 1 Phase, 60 Hz at 3600 RPM, 3720 RPM at no-load. Thank you, Publio

Gfci breaker + outlet in same circuit.breaker tripping [ 4 Answers ]

I have a gfci breaker for a bathroom and there is an additional gfci outlet in the bathroom on the same circuit. The breaker was tripping intermittently over the past week and now will not re-engage. Should I suspect a faulty breaker or is it better to troubleshoot the circuit first? The...


View more questions Search