    Mangleweld's Avatar
    Mangleweld Posts: 1, Reputation: 1
    New Member
     
    #1

    Jun 23, 2008, 01:08 PM
    Generator power transfer switch
    Our power goes off on a frequent basis. If it is off more than 8 hr I need to power up with my own generator 8kw, to prevent spoilage and to run the well. My question is do you have to disconnect the neutral also and run the neutral to the generator or can the neutral be common to both power sources? Also if a transfer switch is installed does it have to have a switching leg for the neutrals? Also if the neutrals do need to be switched can we use a three phase box to accomplish switching the neutral and both power legs for the generator. Thanks JG
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Jun 23, 2008, 01:49 PM
    Answer:

    Maybe.

    The generator should contain a strap from it's neutral to ground of the output connector that can be removed. When that generator is operate din stand-alone mode the strap should be placed back. i.e. not connected to the house.

    1. Strap removed: No need to switch neutral
    2. Strap exists and generator has it's own ground rod. Neutral should be switched.

    Case 1:
    Ground/reference of system supplied though existing panel.

    Case 2:
    Two ground rods in parallel when transfer swich off - Good thing. Lowers ground resistance.
    Here you don't want two neutrals connected to the same place.

    Case 3: Grounds and neutrals both connected always (Not allowed)
    You don't want two references.

    #1 likely for portable generators
    #2 likely for stand alone generators

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

What to look for when purchasing a power generator [ 7 Answers ]

I'm building a emergency home kit and will be purchasing a portable generator for this kit. I'm looking at a 2.4 hp 1000 watt max/960 rated generator, I'm not sure if a 120v, 8 amp ac receptacle can run anything larger than a handtool. Is there some kind of listing of what can be operated and how...

3 wire 220 connecting transfer switch to generator [ 2 Answers ]

I have a manual transfer switch that I want to use between my house circuits and my 5000 watt generator. I have 3 wire #10 receptical existing from the circuit box over to where my generator sets (it is exhausted outside). Can I use this 3 wire line to connect my transfer switch to my generator...

Generator to Well (pressure switch) [ 1 Answers ]

Hello.. Last year when the power went out I managed to hook my Gen to my pressure switch on my well. I tried to do it this year and the second I turn on the power at the generator it blows the braker. Here's what I did. I disconnected the two leads on the out sides of the pressure...

Transfer Switch & Generator Compatibilty [ 3 Answers ]

I have installed a manual transfer switch in my home. It says in the instructions to make sure the neutral is un-bonded to the generator. My Generator has a bonded neutral to the frame. What can I do to make the switch and the Generator compatible? Thanks

Complex Service Entrance/Generator Transfer App [ 24 Answers ]

Information: 1) Electrical engineering degree :) , but not an electrician :( , 2) need help understanding NEC requirements for this application, 3) will have commercial electrician help but want understanding of requirements beforehand, 4) there are no permits, no inspectors, no code requirements...


View more questions Search