    Free wire THHN
    I have been looking in the NEC and can't seem to find the code which states whether THHN can be free wired for low voltage wiring? Anyone Know?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jan 29, 2008, 12:52 PM
    My interpretation is that THHN is not allowed, see NEC 2005 Section 300.3, states, and I paraphrased, "single conductors listed in table 310.13, (which THHN is listed,) must be installed in accordance with any methods listed in Chapter 3", which does not show any method of attaching single wire to a structure freely.

    The closest I could come with that may allow it is Article 398 Open Wiring on Insulators. This method has a few conditions that would be prohibitive to install this wire in this fashion.

    In short, THHN is listed as an insulation that must use a raceway or method listed in Chapter 3.

    You should review Articles 720 Circuits & Equipment less than 50 volts, and,
    Article 725 Class 1, Class 2, Class 3 RC, Signaling, & Power Limited Circuits.

    You need to determine which Class system you are installing, and then look at the limitations of insulations allowed, esp fire rated installations.

    Why not just use LV cable?

    THHN is rated 600 volts, so that is not the issue, the problem is toxic smoke created during a fire, and physical protection of the wire.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #3

    Jan 30, 2008, 03:19 PM
    Out of curiousity, what were you considering, Alarm loop?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Stranded Versus Solid Core THHN Wires [ 18 Answers ]

I'm still learning so pardon the dumb question. In wiring a new addition for 110v and 220v electrical outlets, switches and lights is there a certain time when you would want to use stranded core THHN wire vs solid core THHN wire? I guess in particular I'm referring to when you would use...

How to wire 2 wire fan remote to 3 wire circuit? [ 10 Answers ]

I have a room that has 2 light switchs to the same light, so it is a 3 wire circuit. I bought a fan with a remote and the wall mounted remote has only 2 wires, how can I connect it? Thanks, Pete

Running THHN wire above 8 feet. [ 3 Answers ]

I am wiring a barn/shop area and have run all wiring in EMT conduit except above 8 feet where I have run some ROMEX to lights. My question is: I need one extra wire for a 3-way switch traveler wire. Can I staple this along side of the ROMEX wire above 8' in the hi bay area, or does it have to be in...

Hard wire 3 wire to 4 wire 220 service [ 1 Answers ]

How do I hard wire my 3 wire (red,blk & bare copper wires) 220vac cooktop to the 4 wire (black/white stripe,black/red stripe, blk/blk & bare alum wires) in the house supply j-box ?

3-wire home, 3-wire fan, 2-wire remote [ 9 Answers ]

Greetings, My home is 3-wire. I bought a Hunter ceiling fan (model 23811). The fan came with a remote assy. That I do NOT want to use... The fan has standard 3-wire connections (black, white, blk&white strip, ground). The remote receiver home-side wiring looks to be for 2-wire (blk and white)....


View more questions Search