    #1

    Nov 10, 2006, 07:25 AM
    Feeder Wire for Sub-Panel
    Hello my name is Mark and I have just purchased my first home. I was hoping someone could help me out in determining what size feeder cable I would need to run from my main panel to a detached garage. The length of the run would be 70 feet. The main panel is a 100 amp panel. I would be running 6 shop lights, a handful of 15 amp outlets, and 2 spotlights. I would also like to have room for a little expansion room if need be. Thanks in advance for your help.

    -Mark
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Nov 10, 2006, 08:17 AM
    Without knowing the loads of what will be in the shop, and not wanting to overload the 100 amp main panel, I would suggest using #8 Romex cable, 3 wire with a ground, on a 40 amp breaker in the main panel, and an 8 circuit panel in the garage.

    This may not be enough expansion, but without knowing the connected load of the home, may want to be a bit conservative.

    There is nothing wrong with installing a 100 amp feeder to a 100 amp subpanel in the garage. The 100 amp main breaker to the home will limit how much is used for both the home and garage. Will depend on how much is used at the same time in the home and garage.
    bigpete50's Avatar
    bigpete50 Posts: 2, Reputation: 1
    New Member
     
    #3

    Nov 10, 2006, 08:28 AM
    Thank you very much for your quick response, I really appreciate it. That was just the type of answer I was hoping for. I would rather be safe and conservative then anything else. Thanks again!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Connecting 3 wire to a 4 wire service panel [ 5 Answers ]

I am trying to connect from a 3 wire system at the utility pole to a 4 wire service panel inside a new mobile home. I called an electrician for some advice and was told that I needed to drive an 8ft ground stake and attach a solid copper wire from the stake to the ground bar in the panel. Then I...

Wire at the service panel [ 1 Answers ]

I am installing a GEŽ 30" Free-Standing Electric Range(JBS55WK/CK/BK). It can use a 3 or 4-WIRE CONDUIT INSTALLATION plug from the range to the outlet. I have a double braker space available at the service panel. I have installed brakers into the panel for outlets and lights and then had them...

Feeder line from main panel [ 5 Answers ]

I want to run a feeder line from one building to another in a 2 in. underground conduit.about 100 ft. run what size alum. Wire will I need for 125 amp sub panel

Reduced Neutral for Subpanel Feeder [ 2 Answers ]

Hello, I am adding a sub-panel for a new cooktop and double wall oven. They are rated 9KW and 7.5KW. I already have 1" EMT run from my main panel to a good location under the kitchen in the basement (about 40'). I have some wire and a load center on hand that I would like to use if I can,...

3-wire home, 3-wire fan, 2-wire remote [ 9 Answers ]

Greetings, My home is 3-wire. I bought a Hunter ceiling fan (model 23811). The fan came with a remote assy. That I do NOT want to use... The fan has standard 3-wire connections (black, white, blk&white strip, ground). The remote receiver home-side wiring looks to be for 2-wire (blk and white)....


View more questions Search